VTR 100B LITE Installation and Service manual v2

Table Of Contents
Before Starting the System |
31
Position Description
Remark
1
Outdoor/exhaust air damper Normally open, 230 V 1~, max 0,1 A /
24 VAC 1 A
2
Outdoor/exhaust air damper Reference
3
Outdoor/exhaust air damper Normally closed, 230 V 1~, max 0,1 A /
24 VAC 1 A
4
Sum alarm Normally open, 24 V, max 1 A
5
Sum alarm Reference
6
Sum alarm Normally closed, 24 V, max 1 A
7 GND
Reference
8
Water cooler control signal (AO2)
0–10 V DC
9 GND
Reference
10
Water heater control signal (AO1)
0–10 V DC
11 GND
Reference
12
Bypass damper/Rotor control (AO3)
If used, 0–10 V DC
6.3 External connections on top of the unit
Two of the connections on the main print card are wired to plugs on the unit casing:
connection to an external control panel through a modular connector.
Maximum cable length: 50 m.
Cable type: Flat 4–conductor CEC Phone cable.
External Modbus connector.
Maximum cable length: 90m in cable duct + 10 m in working area.
Cable type: LAN TCP Cat5E 4x2XAWG24 cable.
connection to DI 3 with possibility to configure the fan speeds individually through a potential free on/off switch
1. Connection to DI 3 through an on/off switch
2. Connection to control panel
3. External Modbus connection
4. Cable glands
7 Before Starting the System
When the installation is completed, check that:
The unit is installed in accordance with the instructions
Outdoor and exhaust air dampers and silencers are installed and that the duct system is correctly connected to the
unit
All ducts are sufficiently insulated and installed according to local rules and regulations
Outdoor air intake is positioned with sufficient distance to pollution sources (kitchen ventilator exhaust, central vac-
uum system exhaust or similar)
All external equipment is connected
The unit is correctly wired
The unit is correctly configured and commissioned
The week schedule and airflow settings are correctly programmed.