VTR 100B LITE Installation and Service manual v2

Table Of Contents
40
|
Operation
Menu Level 1 Menu Level 2 Menu Level 3 Explanation
Functions
Digital output
Digital output
1: SF 67%
2: EF 67%
3: Rot ON/OFF
4: ALARM Y/N
5: Dmp Y/N
6: Heater Y/N
Shows The current status of
digital outputs 1–6 (the settings
in the column to the left are
examples).
1: SF 67%: Current set speed of
the supply air fan (shown as
percentage of the maximum
speed).
2: EF 67% Current set speed of
the extract air fan (shown as
percentage of the maximum
speed).
3: Shows if the rotor is active or
not. Unused for unit with counter
flow heat exchanger.
4: Alarm Y/N: Indicates if the
sum. alarm is active or not
5: Dmp OFF: Outdoor/exhaust air
damper is on or off.
6: Heater Y/N: Indicates if the
electrical re-heater is active or
not.
External sensors External sensors
CO2: 0 ppm
RH: 0%
Last valid value is presented for
the bounded sensors.
Highest actual sensor signal
presented via –/modbus/
wireless.
Unbound sensor presented as
(none).
Modbus sensors has priority
over wireless sensors.
Functions
External DI
External DI
Active Wireless: DI1/..
DI20
Assign to:
—/DI-5/DI7
External DI menu only available
if one or several “Input modules”
are bound to the system. Active
wireless DI1-20 is depended on
actual node for “Input module”.
Node shown in “Wireless” menu
which node representing DI
module inputs.
Eg.
Node 1 type: DI. Active wireless
DI1 and DI2
Node 2 type: DI. Active wireless
DI3 and DI4
Node 10 type: DI. Active
wireless DI19 and DI20
Active wireless DI1-20 are
available to assign to DI1-5 and
DI7 for the system in the air
handling unit.
DI6 is not available as selection,
used by the system in the air
handling unit.
Unsigned DI is shown as
(none).
To reset a previously assigned
DI, select “–” and confirm the
selection.
212962 | v02