Commissioning Record

Alarm configuration |
17
52
Malfunction external heating/cooling (SEQ-J)
B No action 5s
53
Filter alarm supply air
B No action 300s
54
Filter alarm extract air B No action 300s
55
Alarm low air flow A
Normal stop
30s
56
Freeze protection guard
A
Fast stop
1s
57
Defrosting guard exchanger
A
Normal stop
30s
58
Fire alarm
A
Fast stop
1s
59
Smoke alarm
A
Fast stop
1s
60
External stop
C
Normal stop
1s
61
External alarm B No action 1s
62
Service stop
C
Normal stop
1s
63
Electric heater is overheated A
Normal stop
1s
65
Low efficiency exchanger
B No action 30m 50%
66
Defrosting alarm
A
Normal stop
1s
67
Rotary exchanger alarm
B No action 30s
68
Extra alarm 1 B No action 5s
69
Extra alarm 2 B No action 5s
70
Extra alarm 3 B No action 5s
162527 | A004