Commissioning Record

24
| Alarm configuration
232
Sensor error freeze protection zone 2
A
Fast stop
1s
233
Sensor error freeze protection zone 3
A
Fast stop
1s
234
Signal error feedback cooler valve
B No action 5s
235
Signal error feedback outdoor air damper
B No action 5s
236
Signal error feedback recirc. damper
B No action 5s
237
Device warning
C No action 1s
238
Device alarm B No action 1s
239
High pressure EATR
A
Normal stop
10s 100 Pa
240
Sensor error pressure EATR
B No action 5s
241
Fail-safe airflow/temperature control
C No action 1s
242
Pre-filter alarm supply air
B No action 300s
243
End-filter alarm supply air
B No action 300s
244
Pre-filter alarm extract air B No action 300s
245
Sensor error pressure pre-filter supply
B No action 5s
246
Sensor error pressure end-filter supply
B No action 5s
247
Sensor error pressure pre-filter extract
B No action 5s