Original instructions Arden 3500 EN .... 13 SE .... 17 NO .... 22 FR .... 27 DE .... 33 NL ....39 ES .... 45 IT .... 51 PL .... 57 RU .... 63 FI .... 69 DK ....
Arden 3500 EN The introduction pages consist mainly of pictures. For translation of the English texts used, see the respective language pages. SE Introduktionssidorna består huvudsakligen av bilder. För översättning av de engelska texter som används, se respektive språksidor. NO Introduksjonssidene består hovedsakelig av bilder. For oversettelse av de engelske tekstene, se de respektive språksidene FR Les pages de présentation contiennent principalement des images.
Arden 3500 C 523 523 B B 595 595 A A 646 646 D 532 302 325 532 325 302 C D Type A B C D ARFEC3510 ARFEC3515 ARFEC3520 [mm] 1057 1567 2073 [mm] 1016 1526 2031 [mm] 1067 1577 2083 [mm] 956 1466 1971 3
Arden 3500 Mounting Fig. 1a: Mounting brackets on delivery. Fig. 1b: Mounting on threaded bars outside the unit. Fig. 2: Mounting on threaded bars inside the unit. Note that the brackets are placed at different heights and therefore threaded rods should be of different lengths.
Arden 3500 Service hatch 90° Fig. 3: Snap fixings Gland PC board FC Fig. 4: PC board FC is integrated within the air curtain at delivery. Water connections DN20 (3/4’’), inside thread A 45 45 80 80 B 70 70 85 85 120 120 A B Fig. 5: The water coil is connected inside the unit through holes which are made (during installation) on the top or the side of the unit, possible places are marked with punch marks.
Arden 3500 Accessories PA34TR Item number 18056 18057 18059 18060 18065 18066 237568 17597 19070 19071 19072 PA34CB PA34VD FH1020 Type PA34TR15* PA34TR20* PA34CB15* PA34CB20* PA34VD15* PA34VD20* FH1020 DTV200S* AR35XTT10* AR35XTT15* AR35XTT20* ARFEC3510/3515 ARFEC3520 ARFEC3510/3515 ARFEC3520 ARFEC3510/3515 ARFEC3520 ARFEC3500W ARFEC3500W ARFEC3510 ARFEC3515 ARFEC3520 DTV200S AR35XTT Consists of 4 pcs 6 pcs 4 pcs 6 pcs 4 pcs 6 pcs 2 pcs Dimensions L: 1 m L: 1 m L: 1 m H: 130-210 mm H: 130-210 mm
Arden 3500 Control systems The air curtain must be supplemented with a control system.
Arden 3500 ARFEC3500 A 4210/5010: 3 Motors 4215/5015: 4 Motors 4220/5020: 6 Motors 4225/5025: 7 Motors M M GND A1 A2 GND Sensor I1 I2 O1O2 N Heating N L PE PE 230V IN Trafo N H1 H2 Motor L FCBASE REA Motor B1 B2 D1 D2 Termination BUS 2 HI LO ON LO GND +12V OFF BUS 1 GND +12V HI M GND 0-10V PWM Alarm 3510: 2 Motors 3515: 3 Motors 3520: 4 Motors 3525: 5 Motors PAFEC/ARFEC 3500 A PAFEC/ARFEC 4200 A PAFEC/ARFEC 5000 A 230V~ Wiring diagrams for control system in the FC manual.
Arden 3500 ARFEC3510/3515 E 3510: 2 Motors 3515: 3 Motors 4210/5010: 3 Motors 4215/5015: 4 Motors M M M TS1 TS2 K2 K1 Inlet sensor Outlet sensor GND GND Sensor I1 I2 O1O2 FCBASEPCB REA L1 L2 L3 N Heating N L PE PE 230V IN Trafo N H1 H2 Motor N GND 0-10V PWM Alarm L Motor B1 B2 D1 D2 Termination A1 A2 BUS 2 HI LO ON LO GND +12V OFF BUS 1 GND +12V HI PAFEC/ARF PAFEC/ARF PAFEC/ARF 230V~ 400V 3~ Wiring diagrams for control system in the FC manual.
Arden 3500 ARFEC3520 E 3520: 4 Motors M M M TS2 TS1 K2 K4 K1 Inlet sensor K3 Outlet sensor GND GND Sensor I1 I2 O1O2 FCBASEPCB REA Heating N L PE PE 230V IN Trafo L1 L2 L3 N N H1 H2 Motor N GND 0-10V PWM Alarm L Motor B1 B2 D1 D2 Termination A1 A2 BUS 2 HI LO ON LO GND +12V OFF BUS 1 GND +12V HI ARFEC3520E 317535 230V~ Wiring diagrams for control system in the FC manual.
Arden 3500 ARFEC3500 W 3510: 3515: 3520: 3525: 4210/5010: 3 Motors 4215/5015: 4 Motors 4220/5020: 6 Motors 4225/5025: 7 Motors 2 Motors 3 Motors 4 Motors 5 Motors M M M Inlet sensor Outlet sensor GND Motor I1 I2 O1O2 N Motor L GND 0-10V PWM Alarm E1 E2 - + Actuator WTA 24V BaseW Sensor GND B1 B2 D1 D2 Termination A1 A2 BUS 2 HI LO ON LO GND +12V OFF BUS 1 GND +12V HI N L PE PE 230V IN Trafo PAFEC/ARFEC 3500 W PAFEC/ARFEC 4200 W PAFEC/ARFEC 5000 W 317531 230V~ Wiring diagrams
Arden 3500 Technical specifications Voltage motor: 230V~ 1 Ambient, no heat - ARFEC3500 A (IP20) Item number Type Output Airflow*1 190544 190548 190552 ARFEC3510A ARFEC3515A ARFEC3520A [kW] 0 0 0 [m3/h] 1000/1900 1550/3000 2250/3800 3 Electrical heat - ARFEC3500 E (IP20) Item Type number 190545 190549 190553 ARFEC3510E09 ARFEC3515E14 ARFEC3520E18 Output steps [kW] 4,5/9,0 6,8/14 9,0/18 Airflow*1 Sound power*2 [m3/h] [°C] [dB(A)] 1000/1900 26/14 76 1550/3000 26/13 77 2250/3800 24/14 78 ∆t*4 2
Arden 3500 EN Installation and operating instructions General Instructions Read these instructions carefully prior to installation and use. Keep this manual for future reference. The product may only be used as set out in the assembly and operating instructions. The guarantee is only valid should the product be used in the manner intended and in accordance with the instructions. Application Arden 3500 is an air curtain for recessed mounting. Recommended installation height 3,5 m.
EN Arden 3500 Unit with electrical heating The unit is connected via the cable gland on one side of the unit or its top. Pierce the gland with a screwdriver before entering the cable. Control supply 230V~ is routed via the motor compartment, secured with preinstalled cable ties, and connected to the PC board. Power supply for heating (400V3~) is routed via the motor compartment, secured with preinstalled cable ties, and connected to the terminal block in the terminal box.
Arden 3500 Temperature control Temperature control of FC maintains the exhaust temperature. Should the temperature exceed the preset value, the overheating alarm will activate. For more information see the FC manual. Overheating The air curtain unit with electrical heating is equipped with an overheat protection. If it is deployed due to overheating, reset as follows: 1. Disconnect the power supply with the isolator switch. 2. Determine the cause of overheating and rectify the fault. 3.
EN Arden 3500 Residual current circuit breaker (E) When the installation is protected by means of a residual current circuit breaker, which trips when the appliance is connected, this may be due to moisture in the heating element. When an appliance containing a heater element has not been used for a long period or stored in a damp environment, moisture can enter the element.