IMO(CE) DKEX KTEX

Maintenance
|
11
8 Maintenance
Caution
Always read the safety information before maintenance or service.
Repair or replacement of components is not permitted on DKEX/KTEX. For other questions about the fan, contact techni-
cal support. Cleaning interval should be in proportion to how fast the impeller becomes dirty. Disassembly of the impel-
ler is not allowed.
Motors are completely or partly covered by antistatic painting or coating, which is able to derivate electric charges. A
repaint may lead to dangerous static charges and is therefore not allowed
Check that:
The installation is accessible for cleaning and inspection work.
No Ex atmosphere is present before switching of the fan.
That the fan is not energized and the current circuit is interrupted and secured against restart.
The impeller has stopped before any maintenance/cleaning begins.
Applicable health and safety regulations are followed (EN50 110, IEC 364).
Danger
Cleaning with fluids when the fan is connected to voltage can cause an electric shock danger to life!
Under no circumstances may a high pressure cleaner or water jet be used.
No aggressive solvents may be used as cleaning agents
The cleaning should be carried out in the air flow and in the in and outlet area.
Loose screws must be attached
If the motor protection has tripped, check that the fan is not blocked. Contact the manufacturer if the fan does not
start after you have checked and reset motor protection.
After cleaning the fan must run for 30 min. at 80–100 % of it’s rated voltage to fully dry out. This allows that any
water that has entered to evaporate.
After maintenance or servicing, check that:
There is no abnormal noise and that the operation is without vibrations.
The impeller balance weights have not been moved and that the impeller blades have not been bent.
141815 | A005