Air Distribution Products AIAS Optimizing Control System User Manual
/24 | User Manual AIAS | 201910 Table of Contents General System Description . . . . . . . . . . . . . . . . . . 3 Detailed Topology . . . . . . . . . . . . . . . . . . . . . . . 5 Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 AIAS „Combox“ . . . . . . . . . . . . . . . . . . . . . . 7 Mobile Configuration and Commissioning Control panel S-E3-DSP . . . . . . . . . . . . . . . .
201910 | User Manual AIAS | 3/24 General System Description AIAS is a pre-programmed, easy configurable and operable control system for optimising the energy consumption in demand oriented building ventilation systems with VAV controllers. The minimal configuration of AIAS system is based on one central control unit called AIAS-Combox. It is a compact DDC-controller with pre-programmed functional blocks for optimizing ventilation system energy consumption.
/24 | User Manual AIAS | 201910 The configuration can be extended by adding next AIAS Combox units each for additional up to 30 rooms aerated by the same AHU. So the configuration can be scaled up to virtually unlimited number. The real limitation is the number of rooms aerated by the same AHU. The master AIAS Combox tops the chain of control signals from all slave units. It generates the power control signals for the Supply and extract fan. Room 15 Room 15 Room 15 Fig.
201910 | User Manual AIAS | 5/24 Detailed Topology The operation of AIAS optimizing system is based on the reading of the position of the VAV controller dampers. The damper position information can be transmitted in two different ways: 1. Analog signal (DC 0-10 V or 0-10 kOhm) These signals are collected in AIAS RIO (remote input/output) module and transferred to AIAS Combox via Exoline communication bus. There can be two RIO modules each with 16 analog inputs used for one Combox.
/24 | User Manual AIAS | 201910 Fig.
201910 | User Manual AIAS | 7/24 Hardware Technical Data and Dimensions Supply voltage 24V AC ±15%, 50…60Hz or 20…36V DC Power requirement 3 VA (without load) +C output + 24 V DC, 0.1 A, short-circuit proof Communication EXOline, Modbus or dial-up connection Port 1, isolated, via a built-in RS485 connector. TCP/IP port available Operating system EXOreal Battery backup Memory and real-time clock, at least 5 years Ambient temperature 0...50°C Dimensions 148 x 123 x 58 mm (W x H x D).
/24 | User Manual AIAS | 201910 Mobile Configuration and Commissioning Control Panel S-E3-DSP Description Directly connected to AIAS “combox” the pocket display module enables access to the system configuration and variables for reading and editing directly at site. Different user authorisation and access levels are adjustable.
201910 | User Manual AIAS | 9/24 AIAS Room Controller RC-C3DOC BUILT-IN TEMPERATURE SENSOR Type NTC, linearised, 15 kOhm Measuring range 0...50°C Accuracy +/-0.5°C at 15...30°C Display type LCD with background illumination LVD, Low Voltage Directive This product conforms with the requirements of European LVD standard IEC 60 730-1. EMC emission and immunity standard. This product conforms to the requirements of the EMC Directive 2004/108/EC through product standards EN 61000-6-1 and EN 61000-6-3.
/24 | User Manual AIAS | 201910 Installation It is recommended to use shielded cables for communication between main controller, room units and damper actuators. These cables must be separated from power supply cables for equipments like motors to prevent interferences. As much distance as possible should exist between communication and power supply cables, especially if they are installed parallel to each another. Maximum length for communication cable is 1000 meters.
201910 | User Manual AIAS | 11/24 Wiring field Terminals to field Sign Device make/ type Description Date Terminals to room/ zone Name Location Wiring AHU, BMS Plant Default/ Predefined/Free Exoline/ Modbus Allocated Address Project AHU (Systemair Topvex / DV etc.
/24 | User Manual AIAS | 201910 Wiring diagram 2: AIAS RIO module
201910 | User Manual AIAS | 13/24 Wiring diagram 3: IRC (Individual Room Control) 1 × VAV with MODBUS communication
/24 | User Manual AIAS | 201910 Wiring diagram 4: IRC (Individual Room Control) 2 × VAV with MODBUS communication
201910 | User Manual AIAS | 15/24 Wiring diagram 5: IRC (Individual Room Control) 1 × VAV with analog damper position feed-back signal
/24 | User Manual AIAS | 201910 Wiring diagram 6: IRC (Individual Room Control) 2 × VAV with analog damper position feed-back signal
201910 | User Manual AIAS | 17/24 System Configuration Addressing The communicating system components like room controllers, VAV controllers, remote I/O modules must have assigned unique addresses identifying them at the bus communication. The unique addresses of the room controllers and the RIO modules communicating on EXOLine are set for each device by the manufacturer. They are composed of two numbers PLA(3 digits), ELA(3 digits).
/24 | User Manual AIAS | 201910 AIAS Configuration Tools The AIAS system is based on pre-programmed software modules that can be assigned to physical objects (sensors, controllers, actors), activated and adjusted in configuration menu by a display tool. The mobile display tool can be connected to AIAS Combox by a cable with RJ12 connector. Lower the main configuration points are shown (pages 17 - 22).
201910 | User Manual AIAS | 19/24 Systemair AIAS Version Id Number 000 000 Address: PLA ELA SUPPLY AIR FAN Act Value; Man-Auto Man Value SUPPLY AIR FAN Output Min Output Max Output Basic system information Language: English Mode Fan Control The fan power setpoint is adjusted by AIAS in position AUTO . Manual setup disables fan power optimizing function . EXTRACT AIR FAN Act Value Man-Auto Man Value SUPPLY AIR FAN P-band I-time The fan power min . and max .
/24 | User Manual AIAS | 201910 CO2 Monitoring MONITORING CO2 Activate RC Mode CO2 Monitoring central activation / deactivation for all connected RC units . Adjustable timer setup or automatic setup command from superior control system by digital input on AIAS Combox . The testing procedure is fully automatic . If some CO2 sensor is detected as malfunctioning, an alarm message with the device address is indicated and recorded in system log .
201910 | User Manual AIAS | 21/24 Dampers Mod 1 Same menu points for VAV controllers Mod 2 ... Mod 30 Setpoint Override Modbus communicating VAV controllers: Rel position VAV actual damper position Vmin Vmax Serial number Malfunction I/O Modules I/O Module 1 AI1 AI2 AI3 AI4 Same menu points for I/O Module 2 AI5 AI6 AI7 AI8 AI9 AI10 AI11 AI12 AI13 AI14 AI15 AI16 VAV controller serial number and actual alarm state RIO module actual signal allocation/values on analog inputs 1 . . .
/24 | User Manual AIAS | 201910 Assignment of the system addresses to the physical devices, I/O values . RC Units RC 1 PLA ELA Room controllers system address setup . Each RC has a label with unique address . Save this address here Same menu points for RC 2 ... RC 30 Dampers Mod 1 Connet RC RC Type Mod 1 Modbus Addr.
201910 | User Manual AIAS | 23/24 I/O Modules Address I/O Module I/O Module Connect State Set the new Address to I/O Module 1 Connect State Connect the second I/O Module Connect State Max 2 RIO modules can be connected to AIAS Combox . Set the addesses (PLA/ELA) that are indicated on the RIO module labels .
/24 | User Manual AIAS | 201910 Alarms announcements recorded here . The red light Event log Event log Access Rights for active alarm . Log on Log on Enter password Cur. level Log off Log off 3 levels of authorisation can be chosen with different possibilities to access and change values: Admin Service User Cur. level Change password Change password for level & °C % -40°C ... +50°C ≤ 95% °C % -20°C ... +40°C ≤ 95% Systemair Production a.s.