CO2 Monitoring
MONITORING CO2
Day of Month
Hour of Day
Duration
Fire Alarm
Highest Damper Pos.
Time Settings
RC 1
RC Units
Same menu points for
RC 2 ... RC 30
MONITORING CO2
Activate
RC Mode
CO2 Monitoring central activation / deactivation for all
connected RC units. Adjustable timer setup or automatic setup
command from superior control system by digital input on AIAS
Combox. The testing procedure is fully automatic. If some CO2
sensor is detected as malfunctioning, an alarm message
with the device address is indicated and recorded
in system log.
FIRE ALARM
Ext. Alarm
Damper Mode
FIRE ALARM
Supply
Exhaust
digital input can evoke pre-adjusted reaction of the IRC
connected to AIAS system. The supply/extract fan power can
be switched to preset value. The VAV damper positions can be
adjusted to open/close/Vmin/Vmax
HIGHEST DAMPER POS.
Supply
Exhaust
over VAV controller expressed in percenta-
ge of damper opening is shown here both,
for supply and extract VAVs.
Time Program
ON/OFF timer for time/calendar
controlled functions
RC 1
Act. Mode
Actual temp.
Room controller, actual operating mode
and value of room temperature.
RC 1
Ocupied setp
Heat
Cool
Adjustable room temp. setpoints for
heating and cooling in occupied mode
RC 1
Unocupied setp
Heat
Cool
Adjustable room temp. setpoints for
heating and cooling in unoccupied mode