Description
The central piece of the AIAS optimizing system for
the demand oriented air handling, ow control and
distribution is the AIAS “combox”. It coordinates the
operation of air handling untit with all the individual
room control elements by a tailored digital control
solution without need of additional coding. It covers
also the communication functions for direct or remote
parametrizing, messaging, management, commissioning,
maintenance and BMS integration. The customized set-
up, recognition and assignment of the system elements
at initial start-up is easy and intuitive using a setup
menu.
The capacity of a single AIAS “combox” is sufcient to
operate with up to 30 individual room VAV-control loops,
where each can contain app. 10 data points (control
and measurement variables). The positions of the VAV-
controllers are examined separately air supply and for
air extract. This enables AIAS “combox” to generate
optimized control values individually for the supply and
the exhaust fan on the AHU.
Hardware
AIAS „Combox“
Technical Data and Dimensions
Supply voltage 24V AC ±15%, 50…60Hz or 20…36V DC
Power requirement 3 VA (without load)
+C output + 24 V DC, 0.1 A, short-circuit proof
Communication
EXOline, Modbus or dial-up connection Port 1,
isolated, via a built-in RS485 connector.
TCP/IP port available
Operating system EXOreal
Battery backup Memory and real-time clock, at least 5 years
Ambient
temperature
0...50°C
Dimensions
148 x 123 x 58 mm (W x H x D). DIN controller
width: 8 1/2.
Protection class IP20
Mounting DIN-rail mounting or cabinet mounting
EMC emissions & immunity standards:
This product conforms to the requirements
of the EMC
Directive 2004/108/EC through product
standards EN 61000-6-1 and EN 61000-6-3.
RoHS:
This product conforms to the Directive
2011/65/EU of the European Parliament
and of the Council.
INPUTS
Analogue inputs,
AI
0...10 V, 0...200 mV, Pt1000, DIN Ni1000,
LGNi1000, 12 bit A/D
Digital inputs,
DI
Floating contact, 24 V DC, congurable for
pulse input
Universal inputs, UI AI or DI (see above)
OUTPUTS
Analogue outputs,
AO
0...10 V, 5 mA, 8 bit D/A, short-circuit proof
Digital outputs, DO Mosfet 24 V AC/DC, 2 A. Totally max 8 A.
24 V DC output 0.1 A, short-circuit proof
Connection 10Base-T/100Base-TX auto-negotiation (RJ45).
Cable length max 100 m (min Cat 5)
Protocol EXOline-TCP
Power requirement + 2,5 VA in addition to the basic requirement
Measurements in mm
SM
NQU
NOP
60
149