L BAL E263

7 Programming
7.1 Select operation mode
Information
Simple installation is possible through the selection of the preprog-
rammed mode of operation.
This determines the basic function of the device, factory set
4.01 .
Mode Function
4.00
Pressure sensor output 0...10 V proportional to measuring range
4.01
Pressure controller (PID): output 0...10 V depending on adjusted
Setpoint and measured actual value.
5.00
Air volume sensor: Output 0...10 V propotional to measuring range
(depending on setting for K-Factor)
5.01
Air volume controller (PID): Output 0...10 V depending on adjusted
Setpoint and measured actual value
7.2 Start-up
Procedure
1. You must mount and connect the device in accordance with
the operating instructions.
2. Double check that all connections are correct.
3. The supply voltage must match the information on the rating
plate.
4. Set the mode, unit and measuring range and adjust the sensor
in the BASE SETUP.
5. Set the parameters for control operation for the modes
4.01
and 5.01 under SETTING.
Information
When saving the Operating Mode, the factory settings are stored.
Therefore all the settings you have made, are lost.
Operating Instructions PCA1000/6000D2 Programming
L-BAL-E263-GB 1551 Index 001 Part.-No. 00163445-42
11/20