L BAL E263

Parameter Display / factory setting
Funktion
Max. Uout - 10.0 V - 10.0 V
Max. output voltage:
10.0...0.0 V
BASE SETUP
Base setup
Mode
4.00 4.01 5.00 5.01
Mode
Units
metric: Pa, m
3
/h, K-Factor
inch: in.wg, cfm, K-Factor US
SI units or Imperial
units (US)
Measuring
Range
1: 0...1000 Pa (0...4.0 in.wg)
2: 0...500 Pa (0...2.0 in.wg)
3: 0...300 Pa (0...1.2 in.wg)
4: 0...200 Pa (0...0.8 in.wg)
PCA1000D2
Adjustable measuring
range
1: 0...6000 Pa (0...24.0 in.wg)
2: 0...4000 Pa (0...16.0 in.wg)
3: 0...3000 Pa (0...12.0 in.wg)
4: 0...2000 Pa (0...8.0 in.wg)
PCA6000D2
Adjustable measuring
range
K-Factor
K-Factor US
- -
75
(697)
75
(697)
Nozzle coefcient (K-
Factor)
following
table
Autozero OFF => ON
Automatic 0 offset
Offset
0 Pa
(0.000 in.wg)
Sensor offset (auto-
matically when Auto-
zero)
Setting range: +/ -
1000 Pa (+/- 4.000
in.wg)
1 Setting range
4.01 : 0..100 % sensor measurung range, 5.01 : 0...Max. Range qV (depending
on K-Factor and sensor measuring range)
2 small value = quick regulation, great value = slow regulation (high stability)
- Parameter for selected mode not available
(xxx) Values for Imperial units (US)
Operating Instructions PCA1000/6000D2 Programming
L-BAL-E263-GB 1551 Index 001 Part.-No. 00163445-42
15/20