7.6 Nozzle coefcient (K-Factor)
Maximum K-Factor depending on the measuring range of the pressure sensor
Range
[Pa]
[in.wg]
200
0.8
300
1.2
500
2.0
1000
4.0
2000
8.0
3000
12.0
4000
16.0
6000
24.0
Max.
K-Factor
US
4596
32767
3752
32767
2906
32767
2055
32500
1453
22980
1186
18763
1027
16250
839
13268
Air volume measuring range [m
3
/h], [cfm] depends on selected
measuring range of pressure senosr [Pa], [in.wg] and selected K-
Factor (US). In menu INFO display for Range qV. Maximum
measuring range at input of each possible maximum K-Factor
(US).
Air ow measuring range: max. 65000 m
3
/h (38257 cfm) depend-
ing on setting of measuring range and K-Factor.
7.7 Zero point adjustment (Autozero / Offset)
A zero-point adjustment is possible if the actual value is not 0 Pa
Δp or 0 m
3
/h qV in pressureless state. A zero point calibration is
possible with the function Autozero.
This may be necessary, for example, in case of heavy thermal
uctuations in the sensor environment or non-vertical mounting.
Procedure
1. Pull off the pressurised hoses.
2. Switch function Autozero in BASE SETUP to ON .
3. The display switches to the actual value display and the value
0 is displayed after zero point calibration has taken place.
4. The necessary difference up to 0 is displayed in the BASE
SETUP under Offset.
Alternatively to the automatic zero point calibration, the offset
value can also be set manually
BASE SETUP / Offset.
Operating Instructions PCA1000/6000D2 Programming
L-BAL-E263-GB 1551 Index 001 Part.-No. 00163445-42