technical documentation manuals 308013008

16
| Installation
7.2.1 Installation of the ventilation system
Preconditions
The air flow of the fan must be able to open the air operated damper (LRK).
Installation duct
Do not place a duct bend directly
before or after the fan!
This can cause damage to the
bearings or other parts of the fan.
The duty point may not be
reachable.
The fan may make noise.
Ensure a direct, smooth and
constant air flow to the device.
Ensure a free exhaust, see the
following pictures.
Install an inlet cone or a channel
section with a length of at least 2.5
x D. It is not recommended to install
the protective guard directly in
front of the impeller (without inlet
cone), as additional noise and a
deterioration of the air
performance may result.
To reduce transmission of vibration
to the duct system, we recommend
flexible connections from our
accessory range, see 5.2.3
Accessories, page 7.
D = nominal diameter
3
1
2
min. 2,5xD
min. 2,5xD
3
1
Inlet cone
2
Protective guard
3
Flexible connection
Distance from the wall/ceiling
Ensure enough distance between the ceiling and the
wall.
The duty point may not be reachable.
The fan may make noise.
If the minimal distances are not possible for construction
reasons, install a deflector in front of the fan in a way
that ensures a direct, smooth and constant flow of air.
Contact with rotating parts must be ruled out at all times
either by ducts of a corresponding length or by
protective grids.
D = Nominal diameter
min. 1xD
1xD
| 008