Commissioning Record

Function settings
|
11
Function
Default setting
Set value
Support control
No
Yes
No
Yes
Start heating room temperature 15 °C °
Stop heating room temperature
21 °C
°
Start cooling room temperature
30 °C
°
Stop cooling room temperature
28 °C
°
Preheater
No
Yes
No
Yes
Start/Stop function
Unit running
When defrosting
Unit running
When defrosting
Preheater setpoint:
-15 °C
°
Exchanger defrosting mode (only
applied for SC, TC units without section
defrosting)
Pressure monitoring Pressure monitoring
Bypass On
Off
On
Off
Stop defrosting
On
Off
On
Off
Outdoor temp. to allow defrosting
18 °C
°
Outdoor temp. for stop of supply air fan
18 °C
°
Max deviation exchanger pressure to
start defrosting
50%
%
Pressure hysteresis to end defrosting
60%
%
Exchanger defrosting mode (only
applied for SC, TC units with section
defrosting)
Section defrosting Section defrosting
Allow fan stop defrosting if exchanger
pressure > max limit
Yes
No
Yes
No
Max allowed deviation exchanger
pressure when defrosting
150%
%
Max deviation exchanger pressure to
start defrosting
25%
%
Pressure hysteresis to end defrosting
60%
%
Setpoint temperature min limit
4 °C
°
Temperature hysteresis to end
defrosting
4 °C
°
Calibration extract air flow
_____________
Calibration exchanger pressure
_____________
162527 | A004