Adjustable range -100…100%.
Example: Start Cooling
If you want Cooling (Sequence-C / configured as DX) to start earlier than the PID
loop, then set -10% in "Start cool" then will DX cooling start when Exchanger
signal is 90% (PID loop signal for exchanger, if "cool recovery" = active).
Sequence Heating Cooling Start
Heating
Start
Cooling
Sequence name
Sequence-A 2 Off 0% 0% Heating
Sequence-B 1 1 0% 0% Exchanger
Sequence-C Off 2 0% -10% 0% Cooling
Sequence-D Off Off 0% 0% Recirculation 1
Sequence-E Off Off 0% 0% Recirculation 2
Sequence-F Off Off 0% 0% Fan heating/cooling
Sequence-G Off Off 0% 0% Heating 2
Sequence-H Off Off 0% 0% Cooling 2
Sequence-I Off Off 0% 0% Exchanger extract
Sequence-J Off Off 0% 0% Extra heating/cooling capacity
3.1 Heating
Activate: Configuration > Function Configuration > Function Activation> Sequence Configure
type
Example: Order heating sequence:
1. ”Exchanger”
2. ”Heating”
3. ”Heating 2”
Sequence Heating Cooling Start
Heating
Start
Cooling
Sequence name
Sequence-A 2 Off 0% 0% Heating
Sequence-B 1 1 0% 0% Exchanger
Sequence-C Off 2 0% 0% Cooling
Sequence-D Off Off 0% 0% Recirculation 1
Sequence-E Off Off 0% 0% Recirculation 2
Sequence-F Off Off 0% 0% Fan heating/cooling
Sequence-G 3 Off Off 0% 0% Heating 2
Sequence-H Off Off 0% 0% Cooling 2
Sequence-I Off Off 0% 0% Exchanger extract
Sequence-J Off Off 0% 0% Extra heating/cooling capacity
: Order heating sequence:
1. ”Exchanger”
2. ”Heating 2”
3. ”Heating”