Configuration Manual

Version Document
A
001
A
ccess V4.X Configuration manual
24 (56) 2018-07-11
3.4 Damper
Activate: Configuration > Function Configuration > Function Activation> Sequence Configure
type
Activate Recirculation (Recirculation 2)
Example: Order heating sequence:
1. ”Exchanger”
2. ”Heating”
3. ”Recirculation”
Sequence Heating Cooling Start
Heating
Start
Cooling
Sequence name
Sequence-A 2 Off 0% 0% Heating
Sequence-B 1 1 0% 0% Exchanger
Sequence-C Off 2 0% 0% Cooling
Sequence-D 3 Off Off 0% 0% Recirculation 1
Sequence-E Off Off 0% 0% Recirculation 2
Sequence-F Off Off 0% 0% Fan heating/cooling
Sequence-G Off Off 0% 0% Heating 2
Sequence-H Off Off 0% 0% Cooling 2
Sequence-I Off Off 0% 0% Exchanger extract
Sequence-J Off Off 0% 0% Extra heating/cooling capacity
Activate Recirculation and Recirculation 2
Example: Order heating sequence:
1. ”Exchanger”
2. ”Heating”
3. ”Recirculation 2”
4. “Recirculation”
Sequence Heating Cooling Start
Heating
Start
Cooling
Sequence name
Sequence-A 2 Off 0% 0% Heating
Sequence-B 1 1 0% 0% Exchanger
Sequence-C Off 2 0% 0% Cooling
Sequence-D 4 Off Off 0% 0% Recirculation 1
Sequence-E 3 Off Off 0% 0% Recirculation 2
Sequence-F Off Off 0% 0% Fan heating/cooling
Sequence-G Off Off 0% 0% Heating 2
Sequence-H Off Off 0% 0% Cooling 2
Sequence-I Off Off 0% 0% Exchanger extract
Sequence-J Off Off 0% 0% Extra heating/cooling capacity
Configure: Configuration > Function Configuration > Function Activation> Sequence Configure
type > Recirculation (Recirculation 2)
Operation settings: Data & Settings > Temperature control > Recirculation (Recirculation 2)