Configuration Manual

Version Document
A
001
A
ccess V4.X Configuration manual
33 (56) 2018-07-11
When the room temperature has fallen 1 K below the set max limit, recirculation
will start again if the start conditions are still fulfilled.
Frequency controlled fans and using recirculation control you can, depending on
the type of fan control, configure a special pressure/flow offset for the setpoint or a
manual output signal for the supply air fan.
Fire/Smoke
Activate: Configuration > Function Configuration > Function Activation
No
Fire
Smoke
Fire+Smoke
Fan settings for Fire function
Configure: Configuration > Function Configuration > Fire/Smoke > Fans
Operation mode when fire alarm
Stopped
Continuons run
Running via normal start/stop conditions
Supply air fan run
Extract air fan run
Supply air fan setpoint type when fire alarm
Off/Auto normal setpoint
Manual setpoint
Manual outputs
Low speed setpoint
Normal speed setpoit
High speed setpoint
Manual setpoint or output (supply air fan)
0..100%
0..
Extract air fan setpoint type when fire alarm
Off/Auto normal setpoint
Manual setpoint
Manual outputs
Low speed setpoint
Normal speed setpoit
High speed setpoint
Manual setpoint or output (Extract air fan)
0..100%
0..
Fire damper
Configure: Configuration > Function Configuration > Fires/Smoke > Fire damper
Mode
Not active
Dampers normally closed
Damper normally opened
Test
No test
Test with unit running
Test with unit stopped