QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008

Table Of Contents
10
| Quick configuration guides
5.4.4 Operation settings
Data & Settings > Temp Control > Supply air
controller
24 Jun 10:31
Min limit supply air
14.0 °C
Max limit supply air
30.0 °C
Step by step:
1.
Select Data & Settings from the navigation icons
2. Select Temperature control
3. Select Room controller
4. Adjust Setpoint room to the desired temperature setpoint
5. Go back to Temperature control (use the navigation path Data & Settings > Temperature control)
6. Select Supply air controller
7. Set Min limit supply air to the lowest permitted supply air temperature
8. Set Max limit supply air to the highest permitted supply air temperature.
5.5 Extended operation
5.5.1 Activation
Select Yes on Extended operation in the Configuration > Functions > Function activation menu.
Overview:
Configuration > Functions > Function activation
24 Jun 10:31
Extended operation
Yes
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Yes on Extended operation.
5.5.2 Configuration
Select which of the configured fan speeds to enable extended operation for in the Configuration > Functions >
Extended operation menu.
Overview:
Configuration > Functions > Extended operation
24 Jun 10:31
Extended operation low speed
No
Extended operation normal speed
Yes
Extended operation high speed
Yes
Step by step:
157618 | A008