Configuration Manual

Version Document
A
001
A
ccess V4.X Configuration manual
10 (56) 2018-07-11
Settings Frost protection (1/2/3)
Settings for stopped and running mode
Settings Exchanger & defrosting
Step control settings for Step start/stop points, min switch time, outdoor temp/fan
speed block of steps etc.)
Step settings
Fan heat/cool settings (Fan compensation)
Pretreatment
Fan control
Activate: Configuration > Function Configuration > Function Activation
Fan control type
1. Pressure
2. Flow
3. Manual
4. External
5. Supply air pressure and extract air slave
6. Supply air pressure and extract air flow slave
7. Extract air pressure and supply air slave
8. Extract air pressure and supply air flow slave
The rotational speed is controlled by output signal (0 – 100%).
A digital Activate signal is normally used for each fan (“Supply air fan start” and
“Extract air fan start”), for sending a start signal to the frequency converters/EC-
motor. The start signal is activated as long as the fan is expected to be running.
For the supply and extract air fans, there are 1..3 individually settable setpoint
values, one corresponding to Low speed, one corresponding to normal speed and
one corresponding to high speed. Changing between the setpoint values is done
using the timer channels for normal low and high speed or using digital input
signals. Extended Operation, Low, normal and high speed, see chap.14.
Pressure
During pressure control, two separate analogue output signals are used for supply
and extract air and two separate analogue input signals for supply and extract air
for pressure transmitters. The fan speeds are controlled via frequency converters,
thereby maintaining constant pressure. The pressure transmitter inputs are
scalable using “Volt minimum/Minimum (pressure)” and “Volt maximum/Maximum
(pressure)”.
Flow
Instead of giving a pressure setpoint value, it is possible to use an airflow volume
value. The value from the pressure transmitter is recalculated to a volume flow
using the formula below and the fans will be controlled to give a constant flow.
Flow = K * P
X
Where K and X are settable constants dependent on the fan size and P is the
differential pressure, measured over the fan. Each fan has its own set of
parameters.
X is normally 0.5 indicating that the flow is proportional to the square root of the
differential pressure.
Flow presentation can be selected, when fan control type not are “Flow”.