QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008

Table Of Contents
About this document |
1
1 About this document
This document describes how to setup functions in your Access controller and contains quick configuration guides for
the most common functions. All available functionality is described in detail in the “Access 4x configuration manual”
available on the online catalogue or Systemair Configurator for products using the Access control platform.
2 How to set up a function
To set up a function in the access controller you need to be logged in as Service to access the configuration menu. After
login you follow a 4-step procedure to successfully setup the function. Please note that not all functions require all four
steps. The general procedure for setting up a function is described below. Function specific configuration guides are
found later in the document.
2.1 Login
Log in with service mode using password 0612.
Overview:
Service
0612
Login
Step by step:
1.
Open the log in window
2.
Select service from drop down list
3.
Type in password 0612
4.
Press Login.
2.2 Activation
Configuration > Functions > Function activation
Activate a function in a list of available functions (e.g. heater).
2.3 Configuration
Configuration > Functions
Select the function's configuration (e.g. if heater is water, electric etc.).
2.4 Allocation
Configuration > I/O allocation settings
Select the I/O (in-/output) placement of the connected signals and sensors. Configure I/O settings (sensor measuring
range, polarity, edit name of sensor/signal etc.).
Caution
Do no use the same in- or output for several functions.
2.5 Operation settings
Data & Settings
Setup how the function will work (e.g. setpoints, limits etc.)
157618 | A008