Commissioning Record

16
| Alarm configuration
6 Alarm configuration
Alarm no.
Name Class Action
Delay
Limit
1
Malfunction supply air fan 1
A
Normal stop
300s
6
Malfunction extract air fan 1
A
Normal stop
300s
11
Alarm supply air fan 1
A
Normal stop
5s
16
Alarm extract air fan 1 A
Normal stop
5s
21
Warning supply air fan 1
C No action 5s
26
Warning extract air fan 1
C No action 5s
38
Malfunction fire damper
A
Normal stop
90s
42
Testing fire damper
C No action 1s
43
Malfunction heating (SEQ-A)
B No action
5s (EL: 60s)
44
Malfunction exchanger (SEQ-B)
B No action 5s
45
Malfunction cooling (SEQ-C)
B No action 5s
46
Malfunction recirculation 1 (SEQ-D)
B No action 5s
47
Malfunction recirculation 2 (SEQ-E)
B No action 5s
48
Malfunction fan setpoint comp (SEQ-F)
B No action 5s
49
Malfunction heating 2 (SEQ-G)
B No action 5s
50
Malfunction cooling 2 (SEQ-H)
B No action 5s
51
Malfunction exchanger extract (SEQ-I)
B No action 5s
162527 | A004