Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
AlaData.Ala_ManualControlMotor1_Status
X
Input Register (3x)
0140
R
Alarm Status
Manual operation external fan motor 1
AlaData.Ala_ManualControlMotor2_Status
X
Input Register (3x)
0141
R
Alarm Status
Manual operation external fan motor 2
AlaData.Ala_ManualControlPretreatment_Status X Input Register (3x) 0142 R 1 Alarm Status Manual operation pretreatment
AlaData.Ala_SensorErrorTempOutdoor_Status
X
Input Register (3x)
0143
R
Alarm Status
Sensor error outdoor air temperature
AlaData.Ala_SensorErrorTempIntake_Status X Input Register (3x) 0144 R 1 Alarm Status Sensor error intake air temperature
AlaData.Ala_SensorErrorTempSupply_Status X Input Register (3x) 0145 R 1 Alarm Status Sensor error supply air temperature
AlaData.Ala_SensorErrorTempExhaust_Status
X
Input Register (3x)
0146
R
Alarm Status
Sensor error exhaust air temperature
AlaData.Ala_SensorErrorTempExtract_Status X Input Register (3x) 0147 R 1 Alarm Status Sensor error extract air temperature
AlaData.Ala_SensorErrorTempRoom1_Status
X
Input Register (3x)
0148
R
Alarm Status
Sensor error room temperature 1
AlaData.Ala_SensorErrorTempRoom2_Status
X
Input Register (3x)
0149
R
Alarm Status
Sensor error room temperature 2
AlaData.Ala_SensorErrorTempRoom3_Status X Input Register (3x) 0150 R 1 Alarm Status Sensor error room temperature 3
AlaData.Ala_SensorErrorTempRoom4_Status
X
Input Register (3x)
0151
R
Alarm Status
Sensor error room temperature 4
AlaData.Ala_SensorErrorPressureSAF_Status
X
Input Register (3x)
0152
R
Alarm Status
Sensor error pressure supply air
AlaData.Ala_SensorErrorPressureEAF_Status X Input Register (3x) 0153 R 1 Alarm Status Sensor error pressure extract air
AlaData.Ala_SensorErrorFlowSAF_Status
X
Input Register (3x)
0154
R
Alarm Status
Sensor error flow supply air
AlaData.Ala_SensorErrorFlowEAF_Status
X
Input Register (3x)
0155
R
Alarm Status
Sensor error flow extract air
AlaData.Ala_SensorPressureExchangerSAF_Status X Input Register (3x) 0156 R 1 Alarm Status Sensor error flow exchanger supply air
AlaData.Ala_SensorPressureExchangerEAF_Status
X
Input Register (3x)
0157
R
Alarm Status
Sensor error pressure exchanger extract air
AlaData.Ala_SensorErrorTempDeicing_Status X Input Register (3x) 0158 R 1 Alarm Status Sensor error defrosting temperature
AlaData.Ala_SensorErrorTempFrost1_Status X Input Register (3x) 0159 R 1 Alarm Status Sensor error freeze protection temperature 1
AlaData.Ala_SensorErrorTempFrost2_Status
X
Input Register (3x)
0160
R
Alarm Status
Sensor error freeze protection temperature 2
AlaData.Ala_SensorErrorTempFrost3_Status X Input Register (3x) 0161 R 1 Alarm Status Sensor error freeze protection temperature 3
AlaData.Ala_SensorErrorCO2_Status
X
Input Register (3x)
0162
R
Alarm Status
Sensor error CO2 room/extract air
AlaData.Ala_SensorErrorHumidityRoom_Status
X
Input Register (3x)
0163
R
Alarm Status
Sensor error humidity room/extract air
AlaData.Ala_SensorErrorHumidityDuct_Status X Input Register (3x) 0164 R 1 Alarm Status Sensor error humidity supply air
AlaData.Ala_SensorErrorTempExtraController_Status
X
Input Register (3x)
0165
R
Alarm Status
Sensor error extra controller
AlaData.Ala_SensorErrorExtCtrlSAF_Status
X
Input Register (3x)
0166
R
Alarm Status
Signal error external control supply air fan
AlaData.Ala_SensorErrorExtCtrlEAF_Status X Input Register (3x) 0167 R 1 Alarm Status Signal error external control extract air fan
AlaData.Ala_SensorErrorHumidityOutdoor_Status
X
Input Register (3x)
0168
R
Alarm Status
Sensor error humidity outdoor
AlaData.Ala_SensorErrorTempExtraSensor1_Status X Input Register (3x) 0169 R 1 Alarm Status Sensor error extra sensor 1
AlaData.Ala_SensorErrorTempExtraSensor2_Status X Input Register (3x) 0170 R 1 Alarm Status Sensor error extra sensor 2
AlaData.Ala_SensorErrorTempExtraSensor3_Status
X
Input Register (3x)
0171
R
Alarm Status
Sensor error extra sensor 3
AlaData.Ala_SensorErrorTempExtraSensor4_Status X Input Register (3x) 0172 R 1 Alarm Status Sensor error extra sensor 4
AlaData.Ala_SensorErrorTempExtraSensor5_Status
X
Input Register (3x)
0173
R
Alarm Status
Sensor error extra sensor 5
AlaData.Ala_SensorErrorExtSupplySetp_Status
X
Input Register (3x)
0174
R
Alarm Status
Sensor error external temperature setpoint
AlaData.Ala_SensorErrorExtFlowSetpoint_Status X Input Register (3x) 0175 R 1 Alarm Status Signal error external flow setpoint
AlaData.Ala_SensorErrorFilterGuard1_Status
X
Input Register (3x)
0176
R
Alarm Status
Sensor error pressure filter supply air
AlaData.Ala_SensorErrorFilterGuard2_Status
X
Input Register (3x)
0177
R
Alarm Status
Sensor error pressure filter extract air
AlaData.Ala_SensorErrorTempEfficiency_Status X Input Register (3x) 0178 R 1 Alarm Status Sensor error efficiency temp
AlaData.Ala_CommErrorDevice_Status
X
Input Register (3x)
0179
R
Alarm Status
Fault communication device
AlaData.Ala_MalfunctionExtraController_Status
X
Input Register (3x)
0180
R
Alarm Status
Malfunction Extra Controller
AlaData.Ala_InternalError_Status X Input Register (3x) 0181 R 1 Alarm Status Internal error
AlaData.Ala_SmokeDetectorService_Status
X
Input Register (3x)
0182
R
Alarm Status
Smoke detector service
AlaData.Ala_SmokeDetectorError_Status X Input Register (3x) 0183 R 1 Alarm Status Smoke detector connection error
AlaData.Ala_MalfunctionPreheater_Status X Input Register (3x) 0184 R 1 Alarm Status Malfunction preheater 4.1-1-00
AlaData.Ala_CommunicationFaultBMS_Status
X
Input Register (3x)
0185
R
Alarm Status
Communication fault BMS master
4.1-1-00
AlaData.Ala_LeakageHeaterValve_Status X Input Register (3x) 0186 R 1 Alarm Status Leakage heater valve 4.1-1-00
AlaData.Ala_SensorErrorTempPreheat_Status
X
Input Register (3x)
0187
R
Alarm Status
Sensor error preheater temperature
4.1-1-00
AlaData.Ala_MalfunctionSAF6_Status
X
Input Register (3x)
0188
R
Alarm Status
Malfunction supply air fan 6
4.3-1-00
Page 4 of 45