Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_AOManual_SequenceY8
R
Holding Register (4x)
0732
RW
AV, 30732
10
Operation override
Control signal SEQ-H if manual mode
VentSettings.S_AOSelect_SequenceY9 X Holding Register (4x) 0733 RW MSV, 30733 1 Operation override Control mode SEQ-I:
(See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY9
R
Holding Register (4x)
0734
RW
AV, 30734
10
Operation override
Control signal SEQ-I if manual mode
VentSettings.S_AOSelect_SequenceY10 X Holding Register (4x) 0735 RW MSV, 30735 1 Operation override Control mode SEQ-J:
(See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY10
R
Holding Register (4x)
0736
RW
AV, 30736
10
Operation override
Control signal SEQ-J if manual mode
VentSettings.S_FreeCoolDayLimit R Holding Register (4x) 0737 RW AV, 30737 10 T Free cooling Outdoor temperature min limit during day to allow start of free cooling
VentSettings.S_FreeCoolHighLimit
R
Holding Register (4x)
0738
RW
AV, 30738
10
T
Free cooling
Outdoor temperature max limit during night to stop free cooling
VentSettings.S_FreeCoolLowLimit R Holding Register (4x) 0739 RW AV, 30739 10 T Free cooling Outdoor temperature min limit during night to stop free cooling
VentSettings.S_FreeCoolRoomLimit
R
Holding Register (4x)
0740
RW
AV, 30740
10
T
Free cooling
Room temperature min limit during night to stop free cooling
VentSettings.S_FreeCoolStartTime
X
Holding Register (4x)
0741
RW
AV, 30741
Free cooling
Start hour free cooling (00-24)
VentSettings.S_FreeCoolStopTime X Holding Register (4x) 0742 RW AV, 30742 1 Free cooling Stop hour free cooling (00-24)
VentSettings.S_FreeCoolHeatBlockTime
I
Holding Register (4x)
0743
RW
AV, 30743
min
Free cooling
Time to block heat output after free cooling
VentSettings.S_CO2StartLimit
R
Holding Register (4x)
0744
RW
AV, 30744
10
ppm
CO₂
Start limit CO₂ fan start/stop function
VentSettings.S_CO2DemandDiff R Holding Register (4x) 0745 RW AV, 30745 10 ppm CO₂ Hysteresis to stop CO₂ fan start/stop function
VentSettings.S_CO2Setpoint
R
Holding Register (4x)
0746
RW
AV, 30746
10
ppm
CO₂
Setpoint CO₂ mixing damper function
VentSettings.S_CO2MinTime I Holding Register (4x) 0747 RW AV, 30747 1 min CO₂ Min run time CO₂ fan start/stop function
VentSettings.S_NeedControl X Holding Register (4x) 0748 RW AV, 30748 1 Support control Enable support control if the unit is stopped
VentSettings.S_NeedHeatStart
R
Holding Register (4x)
0749
RW
AV, 30749
10
T
Support control
Room temperature to start the unit if support heating is active
VentSettings.S_NeedHeatStop R Holding Register (4x) 0750 RW AV, 30750 10 T Support control Room temperature to stop the unit if support heating is active
VentSettings.S_NeedCoolStart
R
Holding Register (4x)
0751
RW
AV, 30751
10
T
Support control
Room temperature to start the unit if support cooling is active
VentSettings.S_NeedCoolStop
R
Holding Register (4x)
0752
RW
AV, 30752
10
T
Support control
Room temperature for stop the unit if support cooling is active
VentSettings.S_NeedMinTime I Holding Register (4x) 0753 RW AV, 30753 1 min Support control Min run time support control
VentSettings.S_FireDampersAutoMode X Holding Register (4x) 0754 RW MSV, 30754 1 - Operation override Running mode fire damper:
Modbus
0=Close
1=Open
2=Auto
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_DeIcingSetpoint R Holding Register (4x) 0755 RW AV, 30756 10 T Unit setting Setpoint temperature defrosting
VentSettings.S_DeIcingHyst
R
Holding Register (4x)
0756
RW
AV, 30757
10
T
Unit setting
Hysteresis to stop defrosting
VentSettings.S_DeIcingMinTime
X
Holding Register (4x)
0757
RW
AV, 30758
Unit setting
Min run time defrosting
VentSettings.S_DeIcingSAFTempStop R Holding Register (4x) 0758 RW AV, 30758 10 T Unit setting Outdoor temperature min limit to stop supply air fan when defrosting
VentSettings.S_HumiditySetpoint
R
Holding Register (4x)
0759
RW
AV, 30759
10
%RH
Humidity control
Setpoint humidity room/extract air
VentSettings.S_HumidityMaxDuct R Holding Register (4x) 0760 RW AV, 30760 10 %RH Humidity control Max limit humidity supply air
VentSettings.S_HumidityHyst
R
Holding Register (4x)
0761
RW
AV, 30761
10
%RH
Humidity control
Hysteresis to start humidity control after stop max limitation
VentSettings.S_HumidityMaxDiff
R
Holding Register (4x)
0762
RW
AV, 30762
10
%RH
Alarm setting
Alarm limit deviation alarm humidity control
VentSettings.S_HumidityStartLimit R Holding Register (4x) 0763 RW AV, 30763 10 % Humidity control Step start point humidity control
VentSettings.S_HumidityStopLimit
R
Holding Register (4x)
0764
RW
AV, 30764
10
%
Humidity control
Step stop point humidity control
VentSettings.S_RoomSetP R Holding Register (4x) 0765 RW AV, 30765 10 T Temperature setting Setpoint room temperature if room temperature control
VentSettings.S_FrostProtSPRun(0) R Holding Register (4x) 0766 RW AV, 30766 10 T Alarm setting Alarm limit freeze protection alarm 1
VentSettings.S_FrostProtSPStop(0)
R
Holding Register (4x)
0767
RW
AV, 30767
10
T
Unit setting
Setpoint freeze protection 1 if standby mode
VentSettings.S_FrostProtPGain(0) R Holding Register (4x) 0768 RW AV, 30768 10 T Unit setting P-band freeze protection 1 if running mode
(setpoint=alarm limit+P-band)
VentSettings.S_FrostProtSPRun(1)
R
Holding Register (4x)
0769
RW
AV, 30769
10
Alarm setting
Alarm limit freeze protection alarm 2
Page 34 of 45