Communication Manual
Table Of Contents
APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
TimePro.TC_Extra4
L
Input Status Register (1x)
0006
R
BV, 20006
Time channel
Extra time channel 4 active
VentActual.A_SumAlarm
L
Input Status Register (1x)
0007
R
BV, 20007
Alarm point
Sum alarm: Unacknowledged A-, B- or C-alarm
VentActual.A_SumAlarmA(0) L Input Status Register (1x) 0008 R BV, 20008 Alarm point Sum alarm: Unacknowledged A-alarm
VentActual.A_SumAlarmB
L
Input Status Register (1x)
0009
R
BV, 20009
Alarm point
Sum alarm: Unacknowledged B-alarm
VentActual.A_SumAlarmC L Input Status Register (1x) 0010 R BV, 20010 Alarm point Sum alarm: Unacknowledged C-alarm
VentActual.A_AlaPt(1) L Input Status Register (1x) 0011 R BV, 20011 Alarm point Malfunction supply air fan 1
VentActual.A_AlaPt(2)
L
Input Status Register (1x)
0012
R
BV, 20012
Alarm point
Malfunction supply air fan 2
VentActual.A_AlaPt(3) L Input Status Register (1x) 0013 R BV, 20013 Alarm point Malfunction supply air fan 3
VentActual.A_AlaPt(4)
L
Input Status Register (1x)
0014
R
BV, 20014
Alarm point
Malfunction supply air fan 4
VentActual.A_AlaPt(5)
L
Input Status Register (1x)
0015
R
BV, 20015
Alarm point
Malfunction supply air fan 5
VentActual.A_AlaPt(6) L Input Status Register (1x) 0016 R BV, 20016 Alarm point Malfunction extract air fan 1
VentActual.A_AlaPt(7)
L
Input Status Register (1x)
0017
R
BV, 20017
Alarm point
Malfunction extract air fan 2
VentActual.A_AlaPt(8)
L
Input Status Register (1x)
0018
R
BV, 20018
Alarm point
Malfunction extract air fan 3
VentActual.A_AlaPt(9) L Input Status Register (1x) 0019 R BV, 20019 Alarm point Malfunction extract air fan 4
VentActual.A_AlaPt(10)
L
Input Status Register (1x)
0020
R
BV, 20020
Alarm point
Malfunction extract air fan 5
VentActual.A_AlaPt(11)
L
Input Status Register (1x)
0021
R
BV, 20021
Alarm point
Alarm supply air fan 1
VentActual.A_AlaPt(12) L Input Status Register (1x) 0022 R BV, 20022 Alarm point Alarm supply air fan 2
VentActual.A_AlaPt(13)
L
Input Status Register (1x)
0023
R
BV, 20023
Alarm point
Alarm supply air fan 3
VentActual.A_AlaPt(14) L Input Status Register (1x) 0024 R BV, 20024 Alarm point Alarm supply air fan 4
VentActual.A_AlaPt(15) L Input Status Register (1x) 0025 R BV, 20025 Alarm point Alarm supply air fan 5
VentActual.A_AlaPt(16)
L
Input Status Register (1x)
0026
R
BV, 20026
Alarm point
Alarm extract air fan 1
VentActual.A_AlaPt(17) L Input Status Register (1x) 0027 R BV, 20027 Alarm point Alarm extract air fan 2
VentActual.A_AlaPt(18)
L
Input Status Register (1x)
0028
R
BV, 20028
Alarm point
Alarm extract air fan 3
VentActual.A_AlaPt(19)
L
Input Status Register (1x)
0029
R
BV, 20029
Alarm point
Alarm extract air fan 4
VentActual.A_AlaPt(20) L Input Status Register (1x) 0030 R BV, 20030 Alarm point Alarm extract air fan 5
VentActual.A_AlaPt(21)
L
Input Status Register (1x)
0031
R
BV, 20031
Alarm point
Warning supply air fan 1
VentActual.A_AlaPt(22)
L
Input Status Register (1x)
0032
R
BV, 20032
Alarm point
Warning supply air fan 2
VentActual.A_AlaPt(23) L Input Status Register (1x) 0033 R BV, 20033 Alarm point Warning supply air fan 3
VentActual.A_AlaPt(24)
L
Input Status Register (1x)
0034
R
BV, 20034
Alarm point
Warning supply air fan 4
VentActual.A_AlaPt(25) L Input Status Register (1x) 0035 R BV, 20035 Alarm point Warning supply air fan 5
VentActual.A_AlaPt(26) L Input Status Register (1x) 0036 R BV, 20036 Alarm point Warning extract air fan 1
VentActual.A_AlaPt(27)
L
Input Status Register (1x)
0037
R
BV, 20037
Alarm point
Warning extract air fan 2
VentActual.A_AlaPt(28) L Input Status Register (1x) 0038 R BV, 20038 Alarm point Warning extract air fan 3
VentActual.A_AlaPt(29)
L
Input Status Register (1x)
0039
R
BV, 20039
Alarm point
Warning extract air fan 4
VentActual.A_AlaPt(30)
L
Input Status Register (1x)
0040
R
BV, 20040
Alarm point
Warning extract air fan 5
VentActual.A_AlaPt(31) L Input Status Register (1x) 0041 R BV, 20041 Alarm point External operation supply air fan
VentActual.A_AlaPt(32)
L
Input Status Register (1x)
0042
R
BV, 20042
Alarm point
External operation extract air fan
VentActual.A_AlaPt(33)
L
Input Status Register (1x)
0043
R
BV, 20043
Alarm point
Extra fan motor 1 running
VentActual.A_AlaPt(34) L Input Status Register (1x) 0044 R BV, 20044 Alarm point Extra fan motor 2 running
VentActual.A_AlaPt(35)
L
Input Status Register (1x)
0045
R
BV, 20045
Alarm point
Malfunction pump heater
VentActual.A_AlaPt(36)
L
Input Status Register (1x)
0046
R
BV, 20046
Alarm point
Malfunction pump cooler
VentActual.A_AlaPt(37) L Input Status Register (1x) 0047 R BV, 20047 Alarm point Malfunction pump exchanger
VentActual.A_AlaPt(38)
L
Input Status Register (1x)
0048
R
BV, 20048
Alarm point
Malfunction fire damper
VentActual.A_AlaPt(39) L Input Status Register (1x) 0049 R BV, 20049 Alarm point Malfunction damper
VentActual.A_AlaPt(40) L Input Status Register (1x) 0050 R BV, 20050 Alarm point Malfunction extra fan motor 1
VentActual.A_AlaPt(41)
L
Input Status Register (1x)
0051
R
BV, 20051
Alarm point
Malfunction extra fan motor 2
VentActual.A_AlaPt(42) L Input Status Register (1x) 0052 R BV, 20052 Alarm point Malfunction adiabatic cooling
VentActual.A_AlaPt(43)
L
Input Status Register (1x)
0053
R
BV, 20053
Alarm point
Malfunction sequence-A
VentActual.A_AlaPt(44)
L
Input Status Register (1x)
0054
R
BV, 20054
Alarm point
Malfunction sequence-B
Page 39 of 45