IMO EC BASICSV REV3

Systemair AB - Industrivägen 3 - SE-739 30 Skinnskatteberg - Tel.: +46 222 440 00 - Fax: +46 222 440 99 - mailbox@systemair.se - www.systemair.com
1/4
DESCRIPTION
EC room controller in 4 versions for control of temperature, humidity or CO
2
and temperature.
Also available in a universal version for 0-10 V input via an external sensor.
EC-BASIC
Technical features
Power: 110-240 V
~
, 50/60 Hz
Power consumption: EC BASIC-T max 0,46 W
EC BASIC-H max 0,46 W
EC BASIC-U max 0,46 W
EC BASIC-C02/T max 1,25 W
Operating temperature: 0-50°C, 10-90%r.H without condensation.
Inputs (only EC Basic-U): 1 analogue input 0-10 V
Outputs: 1 analogue output 0-10 V
(max 1mA)
Working range: EC BASIC-T 0-50°C
EC BASIC-H 0-100 % RH
EC BASIC-U 0-100 %
EC BASIC-C02/T 0-2000 ppm
Manual activation: minimum 600 cycles
Automatic activation: > 100.000 cycles
Dimensions: 88 x 100 x 30,5 mm
Installation: *wall mounting
Impulse voltage: 2,5 kV
Pollution degree: 2
Classication of unit: type 1
Protection class: IP30
Insulation class: class II
CE standard conformity:
EN 60730-1, EN 61000-6-3, EN 61000-6-1
EN 60730-2-9
*The unit must be installed exclusively in contact with a wall. The installa-
tion with spacer that would allow the access to the back of unit is forbidden
Room controller
18/11/2015 Rev. 3
EC BASIC-T Temperature version
TECHNICAL DESCRIPTION
The controller works by comparing the current room temperature with
an adjustable setpoint. It controls a 0-10 V output signal with a PI al-
gorithm in direct or reverse action, based on the setting of jumper JP1.
The output signal is applied to a ventilator.
JP1 closed 1-2: Heating (control signal increases if the actual
value falls below the setpoint)
JP1 closed 2-3 (*): Cooling (control signal increases if the actual
value exceeds the setpoint)
The setpoint is adjusted by knob in the range 5-30°C.
Proportional band and integral time are set using rotary switch SW1:
SW1 0 1 2 3 4 5 6 7
Prop.
band (°C)
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Integral
time (s)
1800 1700 1600 1500 1400 1300 1200 1100
SW1 8 9 A B C D E F (*)
Prop.
band (°C)
4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0
Integral
time (s)
1000 900 800 700 600 500 400 300
(*) factory settings
The range of the voltage applied to the ventilator is dened using the
MIN and MAX knobs. MIN is used to dene the minimum applicable
voltage to the ventilator (0-5 V), while MAX denes the maximum volt-
age (5-10 V). The PI controller will then operate between the relevant
MIN and MAX values.
Example 1: If the MIN value is set to the minimum position and MAX to
the maximum position, the PI controller will work from 0-10 V.
Example 2: If MIN is set to 2 V and MAX is set to 7 V, the PI controller
works from 2 to 7 V.
EC BASIC-CO2/T Temperature + CO
2
version
TECHNICAL DESCRIPTION
The controller works by comparing the input signal with an adjustable
setpoint. It controls a 0-10 V internal signal with a PI algorithm in direct
or reverse action, based on the setting of jumper JP1.
JP1 closed 1-2: Heating (control signal increases if the actual
value falls below the setpoint)
JP1 closed 2-3 (*): Cooling (control signal increases if the actual
value exceeds the setpoint)
The controller also compares current CO
2
levels with an adjustable
setpoint and controls a 0..10 V proportional, secondary internal signal
in direct action.
The output signal applied to the ventilator constitutes the maximum
between internal signal # 1 and internal signal # 2.
The setpoint is adjusted by knob in the range 5-30°C.
The temperature proportional band and integral time are set using
rotary switch SW1:
SW1 0 1 2 3 4 5 6 7
Prop.
band (°C)
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Integral
time (s)
1800 1700 1600 1500 1400 1300 1200 1100
SW1 8 9 A B C D E F (*)
Prop.
band (°C)
4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0
Integral
time (s)
1000 900 800 700 600 500 400 300
(*) factory settings
The CO
2
proportional band is set using rotary switch SW2:
SW2 0 1 2 3 4 5 6 7
Prop.
band
(ppm)
10 25 50 75 100 125 150 175
SW2 8 9 A B (*) C D E F
Prop.
band
(ppm)
200 300 400 500 600 700 800 1000
(*) factory settings
The CO
2
setpoint is set using rotary switch SW3:
SW3 0 (*) 1 2 3 4 5 6 7
Setpoint
(ppm)
350 400 450 500 550 600 650 700
SW3 8 9 A B C D E F
Setpoint
(ppm)
750 800 850 900 950 1000 1200 1500
(*) factory settings
The range of the voltage applied to the ventilator is dened using the
MIN and MAX trimmer. MIN trimmer is used to dene the minimum ap-
plicable voltage to the ventilator (0-5 V), while MAX trimmer denes the
maximum voltage (5-10 V). The PI controller will then operate between
the relevant MIN and MAX values.
Example 1: If the MIN value is set to the minimum position and MAX to
the maximum position, the controller will work from 0-10 V.
Example 2: If MIN is set to 2 V and MAX is set to 7 V, the controller
works from 2-7 V.
EC BASIC-H Humidity version
TECHNICAL DESCRIPTION
The controller works by comparing the current room humidity with an
adjustable setpoint. It controls a 0-10 V output signal with a proportion-
al algorithm in direct or reverse action, based on the setting of jumper
JP1. The output signal is applied to a ventilator.
JP1 closed 1-2: Humidication (control signal increases if the
actual value falls below the setpoint)
JP1 closed 2-3 (*): Dehumidication (control signal increases if the
actual value exceeds the setpoint)
The humidity setpoint is set using rotary switch SW1:
SW1 0 (*) 1 2 3 4 5 6 7
Setpoint
(% RH)
20 25 30 35 40 45 50 55
SW1 8 9 A B C D E F
Setpoint
(% RH)
60 65 70 75 80 85 90 90
(*) factory settings
The proportional band is set using rotary switch SW2:
SW2 0 1 2 3 4 5 6 7
Prop.
band
(% RH)
5 10 15 20 25 30 35 40
SW2 8 9 A B C D E F (*)
Prop.
band
(% RH)
45 50 50 50 50 50 50 50
(*) factory settings
The range of the voltage applied to the ventilator is dened using the
MIN and MAX trimmer. MIN trimmer is used to dene the minimum ap-
plicable voltage to the ventilator (0-5 V), while MAX trimmer denes the
maximum voltage (5-10 V). The P controller will then operate between
the relevant MIN and MAX values.
Example 1: If the MIN value is set to the minimum position and MAX to
the maximum position, the P controller will work from 0-10 V.
Example 2: If MIN is set to 2 V and MAX is set to 7 V, the P controller
works from 2-7 V.
EC BASIC-U Universal version
TECHNICAL DESCRIPTION
The controller works by comparing the input signal with an adjustable
setpoint. It controls a 0-10 V output signal with a PI algorithm in direct
or reverse action, based on the setting of jumper JP1.
The output signal is applied to a ventilator.
JP1 closed 1-2: Control signal increases if the actual value falls
below the setpoint
JP1 closed 2-3 (*): Control signal increases if the actual value
exceeds the setpoint
The universal setpoint is set using rotary switch SW1:
SW1 0 (*) 1 2 3 4 5 6 7
Setpoint
(%)
5 10 20 25 30 35 40 45
SW1 8 9 A B C D E F
Setpoint
(%)
50 55 60 65 70 80 90 95
(*) factory settings
Proportional band and integral time are set using rotary switch SW2:
SW2 0 1 2 3 4 5 6 7
Prop.
band (%)
1 1.5 2 3 5 7 10 14
Integral
time (s)
600 462 356 274 211 163 125 97
SW2 8 9 A B C D E F (*)
Prop.
band (%)
21 31 45 66 96 140 205 300
Integral
time (s)
74 57 44 34 26 20 16 12
(*) factory settings
The range of the voltage applied to the ventilator is dened using the
MIN and MAX trimmer. MIN trimmer is used to dene the minimum ap-
plicable voltage to the ventilator (0-5 V), while MAX trimmer denes the
maximum voltage (5-10 V). The PI controller will then operate between
the relevant MIN and MAX values.
Example 1: If the MIN value is set to the minimum position and MAX to
the maximum position, the PI controller will work from 0-10 V.
Example 2: If MIN is set to 2 V and MAX is set to 7 V, the PI controller
works from 2-7 V.