DESCRIPTION
EC room controller in 4 versions for control of temperature, humidity or CO
2
and temperature.
Also available in a universal version for 0-10 V input via an external sensor.
EC-BASIC
Technical features
Power: 110-240 V
~
, 50/60 Hz
Power consumption: EC BASIC-T max 0,46 W
EC BASIC-H max 0,46 W
EC BASIC-U max 0,46 W
EC BASIC-C02/T max 1,25 W
Operating temperature: 0-50°C, 10-90%r.H without condensation.
Inputs (only EC Basic-U): 1 analogue input 0-10 V
Outputs: 1 analogue output 0-10 V
(max 1mA)
Working range: EC BASIC-T 0-50°C
EC BASIC-H 0-100 % RH
EC BASIC-U 0-100 %
EC BASIC-C02/T 0-2000 ppm
Manual activation: minimum 600 cycles
Automatic activation: > 100.000 cycles
Dimensions: 88 x 100 x 30,5 mm
Installation: *wall mounting
Impulse voltage: 2,5 kV
Pollution degree: 2
Classication of unit: type 1
Protection class: IP30
Insulation class: class II
CE standard conformity:
EN 60730-1, EN 61000-6-3, EN 61000-6-1
EN 60730-2-9
*The unit must be installed exclusively in contact with a wall. The installa-
tion with spacer that would allow the access to the back of unit is forbidden
Room controller
18/11/2015 Rev. 3
EC BASIC-T Temperature version
TECHNICAL DESCRIPTION
The controller works by comparing the current room temperature with
an adjustable setpoint. It controls a 0-10 V output signal with a PI al-
gorithm in direct or reverse action, based on the setting of jumper JP1.
The output signal is applied to a ventilator.
JP1 closed 1-2: Heating (control signal increases if the actual
value falls below the setpoint)
JP1 closed 2-3 (*): Cooling (control signal increases if the actual
value exceeds the setpoint)
The setpoint is adjusted by knob in the range 5-30°C.
Proportional band and integral time are set using rotary switch SW1:
SW1 0 1 2 3 4 5 6 7
Prop.
band (°C)
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Integral
time (s)
1800 1700 1600 1500 1400 1300 1200 1100
SW1 8 9 A B C D E F (*)
Prop.
band (°C)
4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0
Integral
time (s)
1000 900 800 700 600 500 400 300
(*) factory settings
The range of the voltage applied to the ventilator is dened using the
MIN and MAX knobs. MIN is used to dene the minimum applicable
voltage to the ventilator (0-5 V), while MAX denes the maximum volt-
age (5-10 V). The PI controller will then operate between the relevant
MIN and MAX values.
Example 1: If the MIN value is set to the minimum position and MAX to
the maximum position, the PI controller will work from 0-10 V.
Example 2: If MIN is set to 2 V and MAX is set to 7 V, the PI controller
works from 2 to 7 V.
EC BASIC-CO2/T Temperature + CO
2
version
TECHNICAL DESCRIPTION
The controller works by comparing the input signal with an adjustable
setpoint. It controls a 0-10 V internal signal with a PI algorithm in direct
or reverse action, based on the setting of jumper JP1.
JP1 closed 1-2: Heating (control signal increases if the actual
value falls below the setpoint)
JP1 closed 2-3 (*): Cooling (control signal increases if the actual
value exceeds the setpoint)
The controller also compares current CO
2
levels with an adjustable
setpoint and controls a 0..10 V proportional, secondary internal signal
in direct action.
The output signal applied to the ventilator constitutes the maximum
between internal signal # 1 and internal signal # 2.
The setpoint is adjusted by knob in the range 5-30°C.
The temperature proportional band and integral time are set using
rotary switch SW1:
SW1 0 1 2 3 4 5 6 7
Prop.
band (°C)
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Integral
time (s)
1800 1700 1600 1500 1400 1300 1200 1100
SW1 8 9 A B C D E F (*)
Prop.
band (°C)
4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0
Integral
time (s)
1000 900 800 700 600 500 400 300
(*) factory settings
The CO
2
proportional band is set using rotary switch SW2:
SW2 0 1 2 3 4 5 6 7
Prop.
band
(ppm)
10 25 50 75 100 125 150 175
SW2 8 9 A B (*) C D E F
Prop.
band
(ppm)
200 300 400 500 600 700 800 1000
(*) factory settings
The CO
2
setpoint is set using rotary switch SW3:
SW3 0 (*) 1 2 3 4 5 6 7
Setpoint
(ppm)
350 400 450 500 550 600 650 700
SW3 8 9 A B C D E F
Setpoint
(ppm)
750 800 850 900 950 1000 1200 1500
(*) factory settings
The range of the voltage applied to the ventilator is dened using the
MIN and MAX trimmer. MIN trimmer is used to dene the minimum ap-
plicable voltage to the ventilator (0-5 V), while MAX trimmer denes the
maximum voltage (5-10 V). The PI controller will then operate between
the relevant MIN and MAX values.
Example 1: If the MIN value is set to the minimum position and MAX to
the maximum position, the controller will work from 0-10 V.
Example 2: If MIN is set to 2 V and MAX is set to 7 V, the controller
works from 2-7 V.
EC BASIC-H Humidity version
TECHNICAL DESCRIPTION
The controller works by comparing the current room humidity with an
adjustable setpoint. It controls a 0-10 V output signal with a proportion-
al algorithm in direct or reverse action, based on the setting of jumper
JP1. The output signal is applied to a ventilator.
JP1 closed 1-2: Humidication (control signal increases if the
actual value falls below the setpoint)
JP1 closed 2-3 (*): Dehumidication (control signal increases if the
actual value exceeds the setpoint)
The humidity setpoint is set using rotary switch SW1:
SW1 0 (*) 1 2 3 4 5 6 7
Setpoint
(% RH)
20 25 30 35 40 45 50 55
SW1 8 9 A B C D E F
Setpoint
(% RH)
60 65 70 75 80 85 90 90
(*) factory settings
The proportional band is set using rotary switch SW2:
SW2 0 1 2 3 4 5 6 7
Prop.
band
(% RH)
5 10 15 20 25 30 35 40
SW2 8 9 A B C D E F (*)
Prop.
band
(% RH)
45 50 50 50 50 50 50 50
(*) factory settings
The range of the voltage applied to the ventilator is dened using the
MIN and MAX trimmer. MIN trimmer is used to dene the minimum ap-
plicable voltage to the ventilator (0-5 V), while MAX trimmer denes the
maximum voltage (5-10 V). The P controller will then operate between
the relevant MIN and MAX values.
Example 1: If the MIN value is set to the minimum position and MAX to
the maximum position, the P controller will work from 0-10 V.
Example 2: If MIN is set to 2 V and MAX is set to 7 V, the P controller
works from 2-7 V.
EC BASIC-U Universal version
TECHNICAL DESCRIPTION
The controller works by comparing the input signal with an adjustable
setpoint. It controls a 0-10 V output signal with a PI algorithm in direct
or reverse action, based on the setting of jumper JP1.
The output signal is applied to a ventilator.
JP1 closed 1-2: Control signal increases if the actual value falls
below the setpoint
JP1 closed 2-3 (*): Control signal increases if the actual value
exceeds the setpoint
The universal setpoint is set using rotary switch SW1:
SW1 0 (*) 1 2 3 4 5 6 7
Setpoint
(%)
5 10 20 25 30 35 40 45
SW1 8 9 A B C D E F
Setpoint
(%)
50 55 60 65 70 80 90 95
(*) factory settings
Proportional band and integral time are set using rotary switch SW2:
SW2 0 1 2 3 4 5 6 7
Prop.
band (%)
1 1.5 2 3 5 7 10 14
Integral
time (s)
600 462 356 274 211 163 125 97
SW2 8 9 A B C D E F (*)
Prop.
band (%)
21 31 45 66 96 140 205 300
Integral
time (s)
74 57 44 34 26 20 16 12
(*) factory settings
The range of the voltage applied to the ventilator is dened using the
MIN and MAX trimmer. MIN trimmer is used to dene the minimum ap-
plicable voltage to the ventilator (0-5 V), while MAX trimmer denes the
maximum voltage (5-10 V). The PI controller will then operate between
the relevant MIN and MAX values.
Example 1: If the MIN value is set to the minimum position and MAX to
the maximum position, the PI controller will work from 0-10 V.
Example 2: If MIN is set to 2 V and MAX is set to 7 V, the PI controller
works from 2-7 V.