15/38 | CFC-A
Technical Parameters
Legend
L
0,2
(m)Air throw length with terminal velocity 0,2 m/s
L
x
(m)Air throw length calculated for specific terminal velocity
x (m/s)Terminal velocity in range of 0,1 m/s ... 1 m/s
Calculation of Air Throw for Different Terminal Velocities
L
x
= L
0,2
· 0,2/x
Pressure drop and radiated sound power level dependent on air flow volume
Throw length with terminal velocity 0,2 m/s dependent on air flow volume
CFC-A-H-305x305x80-125-SW + ADQ-CFC-A-305x305-SW
Pressure drop & A-weighted sound power level in dB(A)
80 120 160 200 240 m³/h
20 30 40 50 60 70 l/s
25
50
75
Pa
20
CFC-A-H-457x457x80-160-SW + ADQ-CFC-A-457x457-SW
Pressure drop & A-weighted sound power level in dB(A)
100 200 300 400 m³/h
40 60 80 100 120 l/s
50
100
Pa
20
CFC-A-H-305x305x80-125-SW + ADQ-CFC-A-305x305-SW
Throw length (terminal velocity 0.2 m/s)
80 120 160 200 240 m³/h
3
6
m
Horizontal
CFC-A-H-457x457x80-160-SW + ADQ-CFC-A-457x457-SW
Throw length (terminal velocity 0.2 m/s)
100 200 300 400 m³/h
3
6
m
Horizontal