INSTALLATION OPERATION AND MAINTENANCE INSTRUCTION K KV PRIO006

Table Of Contents
2 Use the fast clamps (A) to attach the duct to the product.
Systemair recommends to use FK fast clamps to attach
the duct to the product. The FK fast clamps are available
as an accessory.
Refer to13 Accessory overview page 30 .
A
3 Tighten the fast clamps (A) around the duct and the
product with the supplied screws. Make sure that there is
a distance between the duct and the product to decrease
vibrations transmitted from the product to the duct
system.
4 If you install the product near a duct bend, do these
steps to prevent vibrations, unwanted noise and de-
creased air pressure:
a. Measure the distance (A) between the product and
the duct bend.
b. Make sure that the distance (A) is a minimum of 2.5
x the diameter (B) of the duct system. For circular
ducts, (B) is the nominal diameter. For rectangular
ducts, (B) is the hydraulic diameter.
AA
B
5 Electrical connection
5.1 To do before the electrical
connection
Make sure that the electrical connection agrees with the
product specification on the motor name plate.
Make sure that the environment for electrical connection
is clean and dry.
Make sure that the wiring diagram that is included with the
supply of the product agrees with the terminals in the con-
nection box.
5.2 To connect the product to the
power supply
Complete the electrical connection for the motor. Refer to
the motor wiring diagram that is included with the product.
Make sure that the cross section of the protective earthing
is equal to or larger than the cross section of the phase
conductor.
Install a circuit breaker in the permanent electrical installa-
tion, with a contact opening of a minimum 3 mm at each
pole.
If a residual current device (RCD) is installed, make sure
that it is an all-current sensitive RCD. Consider if the prod-
uct has a frequency converter, uninterruptible power sup-
ply (UPS), or an EC motor. EC motors have a leakage
current to earth that is <=3.5 mA.
5.3 Speed controller for EC
motors
EC motors are controlled through a stepless 0–10 V signal.
Do not use power supply for the speed controller.
Refer to 12.3 Wiring diagrams page 18 and the instruction
manual for the external speed controller.
5.4 Motor protection for EC
motors
EC motors have an integrated motor protection. Reset the
motor protection by disconnecting the fan from power supply
for 60 seconds.
5.5 Speed controller for AC
motors
Note:
The speed controller alternatives are different for different
motor types. Make sure that your motor is compatible with
the speed controller type before you use it.
The speed can be controlled by voltage reduction using a
transformer. It is also possible to control the fan speed with
frequency converter if the installed frequency converter has
built in all-pole sine filter and shielded cables are not needed.
7