Drain pan Installation instructions Document in original language | 277318 · A001 GB
© Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
Contents 1 2 Introduction ...................................................1 1.1 Product overview ...................................1 1.2 Parts enclosed .......................................1 1.3 Intended use .........................................1 Installation.....................................................
Introduction | 1 Introduction If the water coil in Topvex SR is used as a cooler (with cold water) a drain pan must be installed. 1.1 Product overview 1.2 Parts enclosed Drain pan, rivets to attach the drain pan, protective stickers for rivet and grommet holes. 1.3 Intended use Place the drain pan under the water coil to collect possible condensation water. 2 Installation Danger Disconnect the mains power supply to the unit is before performing any maintenance or electrical work.
2 | Installation SR20, 25, 60, 80, 100 SR35, 70 Use a drill to remove the inner coil plate. Use a drill to remove the bottom coil bracket. Attach protective stickers over the holes. The upper coil bracket remains in place.
Installation | SR20, 25, 60, 80, 100 1 SR35, 70 1 Remove the bottom grommet (1) from the water coil and place a protective sticker over the hole. Place the water coil in the drain pan. Place the inner coil plate with the coil in the drain pan. The water coil is placed in the drain pan to ensure the placement with the upper coil bracket. Mark the drill holes using the drain pan as a template.
4 | Installation SR20, 25, 60, 80, 100 SR35, 70 Remove the drain pan and water coil. Drill 4,2 mm holes. Place the water coil in the drain pan and push it in to the air handling unit.
Installation | SR20, 25, 60, 80, 100 SR35, 70 Fasten the inner plate with rivets to the upper coil bracket. X3 Fasten the drain pan with rivets. Put the fan in place and connect the electric wire and tubes. For connection to drains, follow the local demands.
Phone +46 222 440 00 www.systemair.