OPERATION AND MAINTENANCE INSTRUCTION TOPVEX SR TR 254051A003
Table Of Contents
- 1 Overview
- 2 Warnings
- 3 Warnings signs on product
- 4 Product description
- 5 Internal components position
- 6 Start up
- 7 Operation
- 8 Maintenance
- 8.1 Maintenance intervals
- 8.2 How to replace supply/extract air filter
- 8.3 How to clean NaviPad
- 8.4 How to clean the heat exchanger
- 8.5 Control of the heat exchanger
- 8.6 How to clean fans
- 8.7 How to clean hot water heating coil
- 8.8 How to clean electric heating coil
- 8.9 How to clean the extract air louvres and inlet diffusers
- 8.10 Clean the outdoor air intake
- 8.11 How to clean the duct system
- 8.12 Where to reset tripped fuses
- 8.13 How to reset the manual overheat protection (EL units)
- 8.14 How to replace the fan module
- 8.15 How to replace the heat exchanger
- 8.16 Change the internal battery in control unit CU27–C
- 9 Troubleshooting
- 10 Alarms
- 11 Service
- 12 General conditions
Operation
|
15
7.1.5 Configuration
• System settings
• Configuration wizard (Example 4)
• Function configuration (Example 5)
• I/O allocation settings
• Alarm configuration (Example 6)
• PID controllers
The configuration wizard is a menu that simplify the procedure to Activate and Configure common accessories and
functions and Allocate it’s in- and outputs. The wizard makes necessary configurations automatically and guide the user
through limited options.
Example 4: Configuration wizard
Configuration > Configuration wizard
2022–02–04
Set up pressure control
>
Set up cooler
>
Set up changeover
>
Exit to configuration menu > Complete configuration wizard >
If the configuration wizard does not cover the desired accessory or function it can still be configured via the configura-
tion menu.
Example 5: Function configuration
Configuration > Functions > Function activation
2022–02–04
Fan compensation curves
Yes
Support control
No
Air quality control
No
To activate a function go to Function activation. Choose function to activate and set Yes in the following pop-up
menu. Values for the activated function are now visible and can be adjusted in Data Settings.
If required, allocate in- and outputs in I/O allocation settings.
254051 | A003