Configuration Manual

Version Document
A
001
A
ccess V4.X Configuration manual
41 (56) 2018-07-11
Extra time channel 4
Stop delay motor control 1
0.. s
Motor control 2
None
Motor protection
Run indication
Mode motor control 2
Only Digital input
Normal time channel
Extra time channel 4
Stop delay motor control 2
0.. s
Operation settings: Data & Settings > Fan control > Extra fan motor control
Damper
Activate: Configuration > Function Configuration > Function Activation
None
Outdoor
Outdoor+Exhaust
Exhaust
Outdoor damper follow supply air fan and exhaust damper follow extract air fan
Outdoor air damper stop delay
Operation settings: Data & Settings > Fan control > Supply air fan
0 s
Exhaust air damper stop delay
Operation settings: Data & Settings > Fan control > Exhaust air fan
0 s
Extra Indication & outputs
Activate: Configuration > Function Configuration > Extra Indication & outputs
Extra time channel
None
1
2
3
4
Note! Time channel 4 are used also for recirculation
Running indication
No
Yes