Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
AlaData.Ala_SensorErrorTempDeicing_DelayValue
I
Holding Register (4x)
0445
RW
sec
Alarm setting
Alarm delay sensor error defrosting temperature
AlaData.Ala_SensorErrorTempFrost1_DelayValue
I
Holding Register (4x)
0446
RW
sec
Alarm setting
Alarm delay sensor error freeze protection temperature 1
AlaData.Ala_SensorErrorTempFrost2_DelayValue I Holding Register (4x) 0447 RW 1 sec Alarm setting Alarm delay sensor error freeze protection temperature 2
AlaData.Ala_SensorErrorTempFrost3_DelayValue
I
Holding Register (4x)
0448
RW
sec
Alarm setting
Alarm delay sensor error freeze protection temperature 3
AlaData.Ala_SensorErrorCO2_DelayValue I Holding Register (4x) 0449 RW 1 sec Alarm setting Alarm delay sensor error CO2 room/extract air
AlaData.Ala_SensorErrorHumidityRoom_DelayValue I Holding Register (4x) 0450 RW 1 sec Alarm setting Alarm delay sensor error humidity room/extract air
AlaData.Ala_SensorErrorHumidityDuct_DelayValue
I
Holding Register (4x)
0451
RW
sec
Alarm setting
Alarm delay sensor error humidity supply air
AlaData.Ala_SensorErrorTempExtraController_DelayValue I Holding Register (4x) 0452 RW 1 sec Alarm setting Alarm delay sensor error extra controller
AlaData.Ala_SensorErrorExtCtrlSAF_DelayValue
I
Holding Register (4x)
0453
RW
sec
Alarm setting
Alarm delay signal error external control supply air fan
AlaData.Ala_SensorErrorExtCtrlEAF_DelayValue
I
Holding Register (4x)
0454
RW
sec
Alarm setting
Alarm delay signal error external control extract air fan
AlaData.Ala_SensorErrorHumidityOutdoor_DelayValue I Holding Register (4x) 0455 RW 1 sec Alarm setting Alarm delay sensor error humidity outdoor
AlaData.Ala_SensorErrorTempExtraSensor1_DelayValue
I
Holding Register (4x)
0456
RW
sec
Alarm setting
Alarm delay sensor error extra sensor 1
AlaData.Ala_SensorErrorTempExtraSensor2_DelayValue
I
Holding Register (4x)
0457
RW
sec
Alarm setting
Alarm delay sensor error extra sensor 2
AlaData.Ala_SensorErrorTempExtraSensor3_DelayValue I Holding Register (4x) 0458 RW 1 sec Alarm setting Alarm delay sensor error extra sensor 3
AlaData.Ala_SensorErrorTempExtraSensor4_DelayValue
I
Holding Register (4x)
0459
RW
sec
Alarm setting
Alarm delay sensor error extra sensor 4
AlaData.Ala_SensorErrorTempExtraSensor5_DelayValue
I
Holding Register (4x)
0460
RW
sec
Alarm setting
Alarm delay sensor error extra sensor 5
AlaData.Ala_SensorErrorExtSupplySetp_DelayValue I Holding Register (4x) 0461 RW 1 sec Alarm setting Alarm delay sensor error external temperature setpoint
AlaData.Ala_SensorErrorExtFlowSetpoint_DelayValue
I
Holding Register (4x)
0462
RW
sec
Alarm setting
Alarm delay signal error external flow setpoint
AlaData.Ala_SensorErrorFilterGuard1_DelayValue I Holding Register (4x) 0463 RW 1 sec Alarm setting Alarm delay sensor error pressure filter supply air
AlaData.Ala_SensorErrorFilterGuard2_DelayValue I Holding Register (4x) 0464 RW 1 sec Alarm setting Alarm delay sensor error pressure filter extract air
AlaData.Ala_SensorErrorTempEfficiency_DelayValue
I
Holding Register (4x)
0465
RW
sec
Alarm setting
Alarm delay sensor error efficiency temperature exchanger
AlaData.Ala_CommErrorDevice_DelayValue I Holding Register (4x) 0466 RW 1 sec Alarm setting Alarm delay communication fault device
AlaData.Ala_MalfunctionExtraController_DelayValue
I
Holding Register (4x)
0467
RW
sec
Alarm setting
Alarm delay malfunction extra controller
AlaData.Ala_InternalError_DelayValue
I
Holding Register (4x)
0468
RW
sec
Alarm setting
Alarm delay internal error
AlaData.Ala_SmokeDetectorService_DelayValue I Holding Register (4x) 0469 RW 1 sec Alarm setting Alarm delay service smoke detector
AlaData.Ala_SmokeDetectorError_DelayValue
I
Holding Register (4x)
0470
RW
sec
Alarm setting
Alarm delay connection error smoke detector
AlaData.Ala_MalfunctionPreheater_DelayValue
I
Holding Register (4x)
0471
RW
sec
Alarm setting
Alarm delay malfunction preheater
4.1-1-00
AlaData.Ala_CommunicationFaultBMS_DelayValue I Holding Register (4x) 0472 RW 1 sec Alarm setting Alarm delay communication fault BMS master 4.1-1-00
AlaData.Ala_LeakageHeaterValve_DelayValue
I
Holding Register (4x)
0473
RW
min
Alarm setting
Alarm delay leakage heater valve
4.1-1-00
AlaData.Ala_SensorErrorTempPreheat_DelayValue I Holding Register (4x) 0474 RW 1 sec Alarm setting Alarm delay sensor error preheater temperature 4.1-1-00
AlaData.Ala_MalfunctionSAF6_DelayValue I Holding Register (4x) 0475 RW 1 sec Alarm setting Alarm delay malfunction supply air fan 6 4.3-1-00
AlaData.Ala_MalfunctionSAF7_DelayValue
I
Holding Register (4x)
0476
RW
sec
Alarm setting
Alarm delay malfunction supply air fan 7
4.3-1-00
AlaData.Ala_MalfunctionSAF8_DelayValue I Holding Register (4x) 0477 RW 1 sec Alarm setting Alarm delay Malfunction supply air fan 8 4.3-1-00
AlaData.Ala_MalfunctionEAF6_DelayValue
I
Holding Register (4x)
0478
RW
sec
Alarm setting
Alarm delay malfunction extract air fan 6
4.3-1-00
AlaData.Ala_MalfunctionEAF7_DelayValue
I
Holding Register (4x)
0479
RW
sec
Alarm setting
Alarm delay malfunction extract air fan 7
4.3-1-00
AlaData.Ala_MalfunctionEAF8_DelayValue I Holding Register (4x) 0480 RW 1 sec Alarm setting Alarm delay malfunction extract air fan 8 4.3-1-00
AlaData.Ala_AlarmSAF6_DelayValue
I
Holding Register (4x)
0481
RW
sec
Alarm setting
Alarm delay alarm supply air fan 6
4.3-1-00
AlaData.Ala_AlarmSAF7_DelayValue
I
Holding Register (4x)
0482
RW
sec
Alarm setting
Alarm delay alarm supply air fan 7
4.3-1-00
AlaData.Ala_AlarmSAF8_DelayValue I Holding Register (4x) 0483 RW 1 sec Alarm setting Alarm delay alarm supply air fan 8 4.3-1-00
AlaData.Ala_AlarmEAF6_DelayValue
I
Holding Register (4x)
0484
RW
sec
Alarm setting
Alarm delay alarm extract air fan 6
4.3-1-00
AlaData.Ala_AlarmEAF7_DelayValue
I
Holding Register (4x)
0485
RW
sec
Alarm setting
Alarm delay alarm extract air fan 7
4.3-1-00
AlaData.Ala_AlarmEAF8_DelayValue I Holding Register (4x) 0486 RW 1 sec Alarm setting Alarm delay alarm extract air fan 8 4.3-1-00
AlaData.Ala_WarningSAF6_DelayValue
I
Holding Register (4x)
0487
RW
sec
Alarm setting
Alarm delay warning supply air fan 6
4.3-1-00
AlaData.Ala_WarningSAF7_DelayValue I Holding Register (4x) 0488 RW 1 sec Alarm setting Alarm delay warning supply air fan 7 4.3-1-00
AlaData.Ala_WarningSAF8_DelayValue I Holding Register (4x) 0489 RW 1 sec Alarm setting Alarm delay warning supply air fan 8 4.3-1-00
AlaData.Ala_WarningEAF6_DelayValue
I
Holding Register (4x)
0490
RW
sec
Alarm setting
Alarm delay warning extract air fan 6
4.3-1-00
AlaData.Ala_WarningEAF7_DelayValue I Holding Register (4x) 0491 RW 1 sec Alarm setting Alarm delay warning extract air fan 7 4.3-1-00
AlaData.Ala_WarningEAF8_DelayValue
I
Holding Register (4x)
0492
RW
sec
Alarm setting
Alarm delay warning extract air fan 8
4.3-1-00
AlaData.Ala_MalfunctionHeatingZone1_DelayValue
I
Holding Register (4x)
0493
RW
sec
Alarm setting
Alarm delay malfunction heating zone 1
4.3-1-00
Page 25 of 45