Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_FanType X Holding Register (4x) 0586 RW MSV, 30586 1 Fan setting Select fan control type:
Modbus
0=Pressure
1=Flow
2=Manual
3=External
4=Supply air pressure with extract air fan slave
5=Supply air pressure with extract air flow slave
6=Extract air pressure with supply air fan slave
7=Extract air pressure with supply air flow slave
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_SupplySetpoint R Holding Register (4x) 0588 RW AV, 30588 10 Temperature setting Setpoint supply air temperature when constant supply air temperature
function
VentSettings.S_ExtractSetpoint
R
Holding Register (4x)
0589
RW
AV, 30589
10
Temperature setting
Setpoint extract air temperature if extract control
VentSettings.S_SupplySetpointMax
R
Holding Register (4x)
0590
RW
AV, 30590
10
Temperature setting
Max limit supply temperature setpoint if cascade control
VentSettings.S_SupplySetpointMin R Holding Register (4x) 0591 RW AV, 30591 10 Temperature setting Min limit supply temperature setpoint if cascade control
VentSettings.S_SupplySetpOffsetLow
R
Holding Register (4x)
0592
RW
AV, 30592
10
Temperature setting
Offset temperature setpoint if low speed
VentSettings.S_SupplySetpOffsetHigh R Holding Register (4x) 0593 RW AV, 30593 10 Temperature setting Offset temperature setpoint if high speed
VentSettings.S_Curve1_X1 R Holding Register (4x) 0594 RW AV, 30594 10 T Temperature setting Outdoor compensation curve point 1 sensor value
VentSettings.S_Curve1_X2
R
Holding Register (4x)
0595
RW
AV, 30595
10
T
Temperature setting
Outdoor compensation curve point 2 sensor value
VentSettings.S_Curve1_X3 R Holding Register (4x) 0596 RW AV, 30596 10 T Temperature setting Outdoor compensation curve point 3 sensor value
VentSettings.S_Curve1_X4
R
Holding Register (4x)
0597
RW
AV, 30597
10
T
Temperature setting
Outdoor compensation curve point 4 sensor value
VentSettings.S_Curve1_X5
R
Holding Register (4x)
0598
RW
AV, 30598
10
T
Temperature setting
Outdoor compensation curve point 5 sensor value
VentSettings.S_Curve1_X6 R Holding Register (4x) 0599 RW AV, 30599 10 T Temperature setting Outdoor compensation curve point 6 sensor value
VentSettings.S_Curve1_X7
R
Holding Register (4x)
0600
RW
AV, 30600
10
T
Temperature setting
Outdoor compensation curve point 7 sensor value
VentSettings.S_Curve1_X8
R
Holding Register (4x)
0601
RW
AV, 30601
10
T
Temperature setting
Outdoor compensation curve point 8 sensor value
VentSettings.S_Curve1_Y1 R Holding Register (4x) 0602 RW AV, 30602 10 T Temperature setting Outdoor compensation curve point 1 setpoint
VentSettings.S_Curve1_Y2
R
Holding Register (4x)
0603
RW
AV, 30603
10
T
Temperature setting
Outdoor compensation curve point 2 setpoint
VentSettings.S_Curve1_Y3 R Holding Register (4x) 0604 RW AV, 30604 10 T Temperature setting Outdoor compensation curve point 3 setpoint
VentSettings.S_Curve1_Y4 R Holding Register (4x) 0605 RW AV, 30605 10 T Temperature setting Outdoor compensation curve point 4 setpoint
VentSettings.S_Curve1_Y5
R
Holding Register (4x)
0606
RW
AV, 30606
10
T
Temperature setting
Outdoor compensation curve point 5 setpoint
VentSettings.S_Curve1_Y6 R Holding Register (4x) 0607 RW AV, 30607 10 T Temperature setting Outdoor compensation curve point 6 setpoint
VentSettings.S_Curve1_Y7
R
Holding Register (4x)
0608
RW
AV, 30608
10
T
Temperature setting
Outdoor compensation curve point 7 setpoint
VentSettings.S_Curve1_Y8
R
Holding Register (4x)
0609
RW
AV, 30609
10
T
Temperature setting
Outdoor compensation curve point 8 setpoint
VentSettings.S_SAFSetpointSelect X Holding Register (4x) 0610 RW MSV, 30610 1 Fan setting Setpoint selection supply air fan:
Modbus
0=Constant setpoints
1=Offset of normal speed setpoint
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_EAFSetpointSelect X Holding Register (4x) 0611 RW MSV, 30611 1 Fan setting Setpoint selection extract air fan:
(See signal list for SAFSetpointSelect)
VentSettings.S_SAFLowSpeedPressure(0) R Holding Register (4x) 0612 RW AV, 30612 10 P Fan setting Pressure setpoint supply air fan low speed
VentSettings.S_SAFNormalSpeedPressure R Holding Register (4x) 0613 RW AV, 30613 10 P Fan setting Pressure setpoint supply air fan normal speed
VentSettings.S_SAFHighSpeedPressure
R
Holding Register (4x)
0614
RW
AV, 30614
10
P
Fan setting
Pressure setpoint supply air fan high speed
VentSettings.S_EAFLowSpeedPressure(0) R Holding Register (4x) 0615 RW AV, 30615 10 P Fan setting Pressure setpoint extract air fan low speed
VentSettings.S_EAFNormalSpeedPressure
R
Holding Register (4x)
0616
RW
AV, 30616
10
P
Fan setting
Pressure setpoint extract air fan normal speed
VentSettings.S_EAFHighSpeedPressure
R
Holding Register (4x)
0617
RW
AV, 30617
10
P
Fan setting
Pressure setpoint extract air fan high speed