Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_SeqY3PID_ITime
R
Holding Register (4x)
0698
RW
AV, 30698
PID setting
I-time sequence-C
VentSettings.S_SeqY4PID_Pband
R
Holding Register (4x)
0699
RW
AV, 30699
10
PID setting
P-band sequence-D
VentSettings.S_SeqY4PID_ITime R Holding Register (4x) 0700 RW AV, 30700 1 PID setting I-time sequence-D
VentSettings.S_SeqY5PID_Pband
R
Holding Register (4x)
0701
RW
AV, 30701
10
PID setting
P-band sequence-E
VentSettings.S_SeqY5PID_ITime R Holding Register (4x) 0702 RW AV, 30702 1 PID setting I-time sequence-E
VentSettings.S_SeqY6PID_Pband R Holding Register (4x) 0703 RW AV, 30703 10 PID setting P-band sequence-F
VentSettings.S_SeqY6PID_ITime
R
Holding Register (4x)
0704
RW
AV, 30704
PID setting
I-time sequence-F
VentSettings.S_SeqY7PID_Pband R Holding Register (4x) 0705 RW AV, 30705 10 PID setting P-band sequence-G
VentSettings.S_SeqY7PID_ITime
R
Holding Register (4x)
0706
RW
AV, 30706
PID setting
I-time sequence-G
VentSettings.S_SeqY8PID_Pband
R
Holding Register (4x)
0707
RW
AV, 30707
10
PID setting
P-band sequence-H
VentSettings.S_SeqY8PID_ITime R Holding Register (4x) 0708 RW AV, 30708 1 PID setting I-time sequence-H
VentSettings.S_SeqY9PID_Pband
R
Holding Register (4x)
0709
RW
AV, 30709
10
PID setting
P-band sequence-I
VentSettings.S_SeqY9PID_ITime
R
Holding Register (4x)
0710
RW
AV, 30710
PID setting
I-time sequence-I
VentSettings.S_SeqY10PID_Pband R Holding Register (4x) 0711 RW AV, 30711 10 PID setting P-band sequence-J
VentSettings.S_SeqY10PID_ITime
R
Holding Register (4x)
0712
RW
AV, 30712
PID setting
I-time sequence-J
VentSettings.S_AOSelect_Humidity X Holding Register (4x) 0713 RW MSV, 30713 1 Operation override Control mode humidity control:
Modbus
0=Off
1=Manual
2=Auto
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_AOManual_Humidity
R
Holding Register (4x)
0714
RW
AV, 30714
10
Operation override
Control signal humidity control if manual mode
VentSettings.S_AOSelect_ExtraController X Holding Register (4x) 0715 RW MSV, 30715 1 Operation override Control mode extra controller:
(See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_ExtraController
R
Holding Register (4x)
0716
RW
AV, 30716
10
Operation override
Control signal extra controller if manual mode
VentSettings.S_AOSelect_SequenceY1 X Holding Register (4x) 0717 RW MSV, 30717 1 Operation override Control mode SEQ-A:
(See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY1
R
Holding Register (4x)
0718
RW
AV, 30718
10
Operation override
Control signal SEQ-A if manual mode
VentSettings.S_AOSelect_SequenceY2 X Holding Register (4x) 0719 RW MSV, 30719 1 Operation override Control mode SEQ-B:
(See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY2
R
Holding Register (4x)
0720
RW
AV, 30720
10
Operation override
Control signal SEQ-B if manual mode
VentSettings.S_AOSelect_SequenceY3 X Holding Register (4x) 0721 RW MSV, 30721 1 Operation override Control mode SEQ-C:
(See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY3
R
Holding Register (4x)
0722
RW
AV, 30722
10
Operation override
Control signal SEQ-C if manual mode
VentSettings.S_AOSelect_SequenceY4 X Holding Register (4x) 0723 RW MSV, 30723 1 Operation override Control mode SEQ-D:
(See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY4
R
Holding Register (4x)
0724
RW
AV, 30724
10
Operation override
Control signal SEQ-D if manual mode
VentSettings.S_AOSelect_SequenceY5 X Holding Register (4x) 0725 RW MSV, 30725 1 Operation override Control mode SEQ-E:
(See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY5
R
Holding Register (4x)
0726
RW
AV, 30726
10
Operation override
Control signal SEQ-E if manual mode
VentSettings.S_AOSelect_SequenceY6 X Holding Register (4x) 0727 RW MSV, 30727 1 Operation override Control mode SEQ-F:
(See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY6 R Holding Register (4x) 0728 RW AV, 30728 10 Operation override Control signal SEQ-F if manual mode
VentSettings.S_AOSelect_SequenceY7 X Holding Register (4x) 0729 RW MSV, 30729 1 Operation override Control mode SEQ-G:
(See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY7 R Holding Register (4x) 0730 RW AV, 30730 10 Operation override Control signal SEQ-G if manual mode
VentSettings.S_AOSelect_SequenceY8 X Holding Register (4x) 0731 RW MSV, 30731 1 Operation override Control mode SEQ-H:
(See signal list for AOSelect_Humidity)
Page 33 of 45