5.8.3 Allocation
Select I/O (in-/output) placement of where fire alarm activation input, fire damper output and position feedback input
are connected to the controller in the Configuration > I/O allocation settings submenus Digital inputs
and Digital outputs.
Overview:
Configuration > I/O allocation settings > Digital
inputs
24 Jun 10:31
Digital inputs
Device Position
Fire alarm Controller DI5
Feedback fire damper
Controller
DI6
Configuration > I/O allocation settings > Digital
outputs
24 Jun 10:31
Digital outputs
Device Position
Fire damper
Controller DO5
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Digital inputs
4. Select the input connected to the fire alarm contact/sensor (e.g. DI5) as position for Fire alarm
Note:
Step 5-8: Only applicable if fire dampers are configured.
5. Select the input connected to the fire damper position switches (e.g. DI6) as position for Feedback fire damper
6. Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
7. Select Digital outputs
8. Select the output connected to the fire damper (e.g. DO5) as position for Fire damper.