Configuration Manual

Version Document
A
001
A
ccess V4.X Configuration manual
23 (56) 2018-07-11
settings. Therefore, Blocking step 1 will apply to binary steps 1 and 2, Blocking
step 2 to binary steps 3 and 4, and Blocking step 3 to binary steps 5, 6 and 7.
Blocking of DX cooling on cooling pump alarm Corrigo can be configured to block
DX cooling on cooling pump alarm. In- and outputs
Override of reduced speed for DX cooling
Override to normal quantity of air for DX cooling when the unit runs on reduced
quantity of air. The fans can be set to normal operation when cooling is required at
high outdoor temperatures (e.g. >14°C, the same temperature limit as for blocking
of DX cooling).
Step controller
Activate: By configuring Cooler DX, the step switch will be activated in the menu.
Configure: Configuration > Function Configuration > Function Activation> Sequence Configure
type > Step controller 1 (Step controller 2)
Step controller 1 (2)
Input
Select sequence to connect to step controller 1
Step control type
Sequenciel
Binary
Number of step
1
2
3
4
Select number of digital outputs
Hysteresis if low outdoor temperature block
1 °C
Block step signal if alam
No
Yes
Operation settings: Data & Settings > Temperature control > Cooling (Cooling 2)