Configuration Manual

Version Document
A
001
A
ccess V4.X Configuration manual
40 (56) 2018-07-11
The extra controller can also be used for humidity control. The cooling battery will
be used for dehumidification if the room/extract air humidity is too high. The
function uses the sensor “Extra unit temp” and is placed immediately after the
cooling battery. The function also requires use of a room humidity or extract air
humidity sensor.
Example:
If the room humidity exceeds the setpoint for the function, the cooling battery will
be controlled by the external controller. The heater is controlled normally. When
the room humidity falls below the setpoint once more, the cooling control will return
to normal control. A hysteresis of 1 % is added to the function.
The function can be used for “Cascaded room temperature control”, “Cascade
connected extract air temperature control”, “Outdoor compensated room
temperature control” as well as “Outdoor compensated extract air control”.
An alarm will be triggered if “Extra controller” is in manual position or if a sensor
error occurs.
Operation settings: Data & settings > Temperature control > Supply air controller
Setpoint extra controller
18 °C
Temperature extra controller
Actual value for Extra temperature controller
External switch (External stop)
Activate: Configuration > Function Configuration > Function Activation
No
Yes
The signal “External stop” will stop the unit, even if the time channel or one of the
signals “Extended Operation, Low, “Extended Operation, Normal” or “Extended
Operation High” says it should stay in running mode.
External motor control
Activate: Configuration > Function Configuration > Function Activation
No
One fan control
Two fan control
Extra fan motor control
Configure: Configuration > Function Configuration > Extra fan motor control
Motor control 1
None
Motor protection
Run indication
Mode motor control 1
Only Digital input
Normal time channel