Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
AlaData.Ala_EATROverpressure_Status
X
Input Register (3x)
0238
R
Alarm Status
High pressure EATR
4.5-1-00
AlaData.Ala_SensorErrorEATR_Status
X
Input Register (3x)
0239
R
Alarm Status
Sensor error pressure EATR
4.5-1-00
AlaData.Ala_FailSafe_Status X Input Register (3x) 0240 R 1 Alarm Status Fail-safe airflow/temperature control 4.6-1-00
AlaData.Ala_FilterGuard3_Status
X
Input Register (3x)
0241
R
Alarm Status
Pre-filter alarm supply air
4.6-1-00
AlaData.Ala_FilterGuard4_Status X Input Register (3x) 0242 R 1 Alarm Status End-filter alarm supply air 4.6-1-00
AlaData.Ala_FilterGuard5_Status X Input Register (3x) 0243 R 1 Alarm Status Pre-filter alarm extract air 4.6-1-00
AlaData.Ala_SensorErrorFilterGuard3_Status
X
Input Register (3x)
0244
R
Alarm Status
Sensor error pressure pre-filter supply air
4.6-1-00
AlaData.Ala_SensorErrorFilterGuard4_Status X Input Register (3x) 0245 R 1 Alarm Status Sensor error pressure end-filter supply air 4.6-1-00
AlaData.Ala_SensorErrorFilterGuard5_Status
X
Input Register (3x)
0246
R
Alarm Status
Sensor error pressure pre-filter extract air
4.6-1-00
VentActual.A_AnalogInput(1)
R
Input Register (3x)
0250
R
AV, 40250
10
Analogue input
Actual value AI1
VentActual.A_AnalogInput(2) R Input Register (3x) 0251 R AV, 40251 10 Analogue input Actual value AI2
VentActual.A_AnalogInput(3)
R
Input Register (3x)
0252
R
AV, 40252
10
Analogue input
Actual value AI3
VentActual.A_AnalogInput(4)
R
Input Register (3x)
0253
R
AV, 40253
10
Analogue input
Actual value AI4
VentActual.A_AnalogInput(5) R Input Register (3x) 0254 R AV, 40254 10 Analogue input Actual value AI5 (CU283W-4: UI1)
VentActual.A_AnalogInput(6)
R
Input Register (3x)
0255
R
AV, 40255
10
Analogue input
Actual value AI6 (CU283W-4: UI2)
VentActual.A_AnalogInput(7)
R
Input Register (3x)
0256
R
AV, 40256
10
Analogue input
Actual value AI7 (CU283W-4: UI3)
VentActual.A_AnalogInput(8) R Input Register (3x) 0257 R AV, 40257 10 Analogue input Actual value AI8 (CU283W-4: UI4)
VentActual.A_AnalogInputExp1(1)
R
Input Register (3x)
0258
R
AV, 40258
10
Analogue input
Actual value exp.unit 1 AI1
VentActual.A_AnalogInputExp1(2) R Input Register (3x) 0259 R AV, 40259 10 Analogue input Actual value exp.unit 1 AI2
VentActual.A_AnalogInputExp1(3) R Input Register (3x) 0260 R AV, 40260 10 Analogue input Actual value exp.unit 1 AI3
VentActual.A_AnalogInputExp1(4)
R
Input Register (3x)
0261
R
AV, 40261
10
Analogue input
Actual value exp.unit 1 AI4
VentActual.A_AnalogInputExp1(5) R Input Register (3x) 0262 R AV, 40262 10 Universal input Actual value exp.unit 1 analog UI1
VentActual.A_AnalogInputExp1(6)
R
Input Register (3x)
0263
R
AV, 40263
10
Universal input
Actual value exp.unit 1 analog UI2
VentActual.A_AnalogInputExp1(7)
R
Input Register (3x)
0264
R
AV, 40264
10
Universal input
Actual value exp.unit 1 analog UI3
VentActual.A_AnalogInputExp1(8) R Input Register (3x) 0265 R AV, 40265 10 Universal input Actual value exp.unit 1 analog UI4
VentActual.A_AnalogInputExp2(1)
R
Input Register (3x)
0266
R
AV, 40266
10
Analogue input
Actual value exp.unit 2 AI1
VentActual.A_AnalogInputExp2(2)
R
Input Register (3x)
0267
R
AV, 40267
10
Analogue input
Actual value exp.unit 2 AI2
VentActual.A_AnalogInputExp2(3) R Input Register (3x) 0268 R AV, 40268 10 Analogue input Actual value exp.unit 2 AI3
VentActual.A_AnalogInputExp2(4)
R
Input Register (3x)
0269
R
AV, 40269
10
Analogue input
Actual value exp.unit 2 AI4
VentActual.A_AnalogInputExp2(5) R Input Register (3x) 0270 R AV, 40270 10 Universal input Actual value exp.unit 2 analog UI1
VentActual.A_AnalogInputExp2(6) R Input Register (3x) 0271 R AV, 40271 10 Universal input Actual value exp.unit 2 analog UI2
VentActual.A_AnalogInputExp2(7)
R
Input Register (3x)
0272
R
AV, 40272
10
Universal input
Actual value exp.unit 2 analog UI3
VentActual.A_AnalogInputExp2(8) R Input Register (3x) 0273 R AV, 40273 10 Universal input Actual value exp.unit 2 analog UI4
VentActual.A_AnalogInput(9)
R
Input Register (3x)
0274
R
AV, 40274
10
Analogue input
Actual value AI9
4.4-1-00
VentActual.A_AnalogInput(10)
R
Input Register (3x)
0275
R
AV, 40275
10
Analogue input
Actual value Smoke
4.4-1-00
VentActual.A_AnalogInput(11) R Input Register (3x) 0276 R AV, 40276 10 Universal input Actual value analog UI1 4.4-1-00
VentActual.A_AnalogInput(12)
R
Input Register (3x)
0277
R
AV, 40277
10
Universal input
Actual value analog UI2
4.4-1-00
VentActual.A_AnalogInput(13)
R
Input Register (3x)
0278
R
AV, 40278
10
Universal input
Actual value analog UI3
4.4-1-00
VentActual.A_AnalogInput(14) R Input Register (3x) 0279 R AV, 40279 10 Universal input Actual value analog UI4 4.4-1-00
VentActual.A_AI_OutDoorTemp
R
Input Register (3x)
0290
R
AV, 40290
10
T
AI function
Actual value outdoor temperature
VentActual.A_AI_IntakeAirTemp
R
Input Register (3x)
0291
R
AV, 40291
10
T
AI function
Actual value intake air temperature
VentActual.A_AI_SupplyAirTemp R Input Register (3x) 0292 R AV, 40292 10 T AI function Actual value supply air temperature
VentActual.A_AI_ExhaustAirTemp
R
Input Register (3x)
0293
R
AV, 40293
10
T
AI function
Actual value exhaust air temperature
VentActual.A_AI_ExtractAirTemp R Input Register (3x) 0294 R AV, 40294 10 T AI function Actual value extract air temperature
VentActual.A_AI_RoomTemp1(0) R Input Register (3x) 0295 R AV, 40295 10 AI function Actual value room temperature 1
VentActual.A_AI_RoomTemp2
R
Input Register (3x)
0296
R
AV, 40296
10
AI function
Actual value room temperature 2
VentActual.A_AI_RoomTemp3 R Input Register (3x) 0297 R AV, 40297 10 AI function Actual value room temperature 3
VentActual.A_AI_RoomTemp4
R
Input Register (3x)
0298
R
AV, 40298
10
AI function
Actual value room temperature 4
VentActual.A_AI_SAFPressure
R
Input Register (3x)
0299
R
AV, 40299
10
P
AI function
Actual value supply air pressure
Page 6 of 45