Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentComActual.CA_MotorCurrentSAF(8)
R
Input Register (3x)
0553
R
AV, 40553
10
Fan data
Motor current supply air fan 8
4.3-1-00
VentComActual.CA_MotorCurrentEAF(6)
R
Input Register (3x)
0554
R
AV, 40554
10
Fan data
Motor current extract air fan 6
4.3-1-00
VentComActual.CA_MotorCurrentEAF(7) R Input Register (3x) 0555 R AV, 40555 10 Fan data Motor current extract air fan 7 4.3-1-00
VentComActual.CA_MotorCurrentEAF(8)
R
Input Register (3x)
0556
R
AV, 40556
10
Fan data
Motor current extract air fan 8
4.3-1-00
VentComActual.CA_MotorPowerSAF(6) R Input Register (3x) 0557 R AV, 40557 10 Fan data Motor power supply air fan 6 4.3-1-00
VentComActual.CA_MotorPowerSAF(7) R Input Register (3x) 0558 R AV, 40558 10 Fan data Motor power supply air fan 7 4.3-1-00
VentComActual.CA_MotorPowerSAF(8)
R
Input Register (3x)
0559
R
AV, 40559
10
Fan data
Motor power supply air fan 8
4.3-1-00
VentComActual.CA_MotorPowerEAF(6) R Input Register (3x) 0560 R AV, 40560 10 Fan data Motor power extract air fan 6 4.3-1-00
VentComActual.CA_MotorPowerEAF(7)
R
Input Register (3x)
0561
R
AV, 40561
10
Fan data
Motor power extract air fan 7
4.3-1-00
VentComActual.CA_MotorPowerEAF(8)
R
Input Register (3x)
0562
R
AV, 40562
10
Fan data
Motor power extract air fan 8
4.3-1-00
VentComActual.CA_ActiveFaultSAF(6) I Input Register (3x) 0563 R AV, 40563 1 Fan data Error code supply air fan 6 4.3-1-00
VentComActual.CA_ActiveFaultSAF(7)
I
Input Register (3x)
0564
R
AV, 40564
Fan data
Error code supply air fan 7
4.3-1-00
VentComActual.CA_ActiveFaultSAF(8)
I
Input Register (3x)
0565
R
AV, 40565
Fan data
Error code supply air fan 8
4.3-1-00
VentComActual.CA_ActiveFaultEAF(6) I Input Register (3x) 0566 R AV, 40566 1 Fan data Error code extract air fan 6 4.3-1-00
VentComActual.CA_ActiveFaultEAF(7)
I
Input Register (3x)
0567
R
AV, 40567
Fan data
Error code extract air fan 7
4.3-1-00
VentComActual.CA_ActiveFaultEAF(8)
I
Input Register (3x)
0568
R
AV, 40568
Fan data
Error code extract air fan 8
4.3-1-00
VentComActual.CA_ActualSpeedSAF(6) R Input Register (3x) 0569 R AV, 40569 10 Fan data Actual speed supply air fan 6 4.3-1-00
VentComActual.CA_ActualSpeedSAF(7)
R
Input Register (3x)
0570
R
AV, 40570
10
Fan data
Actual speed supply air fan 7
4.3-1-00
VentComActual.CA_ActualSpeedSAF(8) R Input Register (3x) 0571 R AV, 40571 10 Fan data Actual speed supply air fan 8 4.3-1-00
VentComActual.CA_ActualSpeedEAF(6) R Input Register (3x) 0572 R AV, 40572 10 Fan data Actual speed extract air fan 6 4.3-1-00
VentComActual.CA_ActualSpeedEAF(7)
R
Input Register (3x)
0573
R
AV, 40573
10
Fan data
Actual speed extract air fan 7
4.3-1-00
VentComActual.CA_ActualSpeedEAF(8) R Input Register (3x) 0574 R AV, 40574 10 Fan data Actual speed extract air fan 8 4.3-1-00
VentComActual.CA_AccumPowerSAF(6)
R
Input Register (3x)
0575
R
AV, 40575
10
Fan data
Accumulated power supply air fan 6
4.3-1-00
VentComActual.CA_AccumPowerSAF(7)
R
Input Register (3x)
0576
R
AV, 40576
10
Fan data
Accumulated power supply air fan 7
4.3-1-00
VentComActual.CA_AccumPowerSAF(8) R Input Register (3x) 0577 R AV, 40577 10 Fan data Accumulated power supply air fan 8 4.3-1-00
VentComActual.CA_AccumPowerEAF(6)
R
Input Register (3x)
0578
R
AV, 40578
10
Fan data
Accumulated power extract air fan 6
4.3-1-00
VentComActual.CA_AccumPowerEAF(7)
R
Input Register (3x)
0579
R
AV, 40579
10
Fan data
Accumulated power extract air fan 7
4.3-1-00
VentComActual.CA_AccumPowerEAF(8) R Input Register (3x) 0580 R AV, 40580 10 Fan data Accumulated power extract air fan 8 4.3-1-00
VentActual.A_SupplyPID_SetP_Cool
R
Input Register (3x)
0581
R
AV, 40581
10
T
Unit information
Cooling setpoint supply air temperature
4.3-1-00
VentActual.A_SupplyPID_SetP_Heat R Input Register (3x) 0582 R AV, 40582 10 T Unit information Heating setpoint supply air temperature 4.3-1-00
VentActual.A_DeHumidity_SetP R Input Register (3x) 0583 R AV, 40583 10 %RH Unit information Dehumidification setpoint 4.3-1-00
VentActual.A_Humidity_SetP
R
Input Register (3x)
0584
R
AV, 40584
10
%RH
Unit information
Humidification setpoint
4.3-1-00
VentActual.A_HumidityMode X Input Register (3x) 0585 R MSV, 40585 1 Unit information Humidity control mode
Modbus
0=Not active
1=Humidification
2=Dehumidification
Bacnet
+1 offset for corresponding Modbus
4.3-1-00
VentActual.A_AI_FeedbackCoolerValve
R
Input Register (3x)
0586
R
AV, 40586
10
%
AI function
Actual value position feedback cooler valve
4.6-1-00
VentActual.A_AI_FeedbackOutdoorAirDamper
R
Input Register (3x)
0587
R
AV, 40587
10
%
AI function
Actual value position feedback outdoor air damper
4.6-1-00
VentActual.A_AI_FeedbackRecircAirDamper R Input Register (3x) 0588 R AV, 40588 10 % AI function Actual value position feedback recirculation damper 4.6-1-00
VentActual.A_AI_EATRDPT
R
Input Register (3x)
0589
R
10
Pa
AI function
Actual value pressure EATR
4.5-1-00
VentComActual.CA_DCVoltageSAF(1)
R Input Register (3x) 0590 R AV, 40590 10 V Fan data DC-link voltage, Supply air fan 1 4.6-1-00
VentComActual.CA_DCVoltageSAF(2)
R Input Register (3x) 0591 R AV, 40591 10 V Fan data DC-link voltage, Supply air fan 2 4.6-1-00
VentComActual.CA_DCVoltageSAF(3)
R
Input Register (3x)
0592
R
AV, 40592
10
V
Fan data
DC-link voltage, Supply air fan 3
4.6-1-00
VentComActual.CA_DCVoltageSAF(4)
R Input Register (3x) 0593 R AV, 40593 10 V Fan data DC-link voltage, Supply air fan 4 4.6-1-00
VentComActual.CA_DCVoltageSAF(5)
R
Input Register (3x)
0594
R
AV, 40594
10
V
Fan data
DC-link voltage, Supply air fan 5
4.6-1-00
VentComActual.CA_DCVoltageSAF(6)
R
Input Register (3x)
0595
R
AV, 40595
10
V
Fan data
DC-link voltage, Supply air fan 6
4.6-1-00
Page 13 of 45