Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_RecircTempControl X Holding Register (4x) 0791 RW MSV, 30791 1 Recirculation Supply air temperature control if recirculation:
Modbus
0=No temperature control
1=Heating/cooling
2=Only heating
3=Only cooling
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_RecircMaxRoomTemp R Holding Register (4x) 0792 RW AV, 30792 10 Recirculation If higher room temp when Recirculation run recirculation damper is closed
and fresh air damper is opend
VentSettings.S_RecircFreeCool X Holding Register (4x) 0793 RW AV, 30793 1 Recirculation Allow free cooling if recirculation
VentSettings.S_RecircSAFOffset
R
Holding Register (4x)
0794
RW
AV, 30794
Recirculation
Offset pressure/flow supply air fan if recirculation
4.3-1-00
VentSettings.S_RecircEAFOffset R Holding Register (4x) 0795 RW AV, 30795 1 Recirculation Offset pressure/flow extract air fan if recirculation (this is not used) 4.3-1-00
VentSettings.S_RecircSetPOffset
R
Holding Register (4x)
0796
RW
AV, 30796
10
Recirculation
Offset for recirculation setpoint
VentSettings.S_FilterAlarmTime I Holding Register (4x) 0797 RW AV, 30797 1 Alarm setting Time (in months) for alarm service interval counter
VentSettings.S_ExtraSensor1HighLimit(0)
R
Holding Register (4x)
0798
RW
AV, 30798
10
Alarm setting
Alarm high limit extra sensor 1
VentSettings.S_ExtraSensor2HighLimit
R
Holding Register (4x)
0799
RW
AV, 30799
10
Alarm setting
Alarm high limit extra sensor 2
VentSettings.S_ExtraSensor3HighLimit R Holding Register (4x) 0800 RW AV, 30800 10 Alarm setting Alarm high limit extra sensor 3
VentSettings.S_ExtraSensor4HighLimit
R
Holding Register (4x)
0801
RW
AV, 30801
10
Alarm setting
Alarm high limit extra sensor 4
VentSettings.S_ExtraSensor5HighLimit
R
Holding Register (4x)
0802
RW
AV, 30802
10
Alarm setting
Alarm high limit extra sensor 5
VentSettings.S_ExtraSensor1LowLimit(0) R Holding Register (4x) 0803 RW AV, 30803 10 Alarm setting Alarm low limit extra sensor 1
VentSettings.S_ExtraSensor2LowLimit
R
Holding Register (4x)
0804
RW
AV, 30804
10
Alarm setting
Alarm low limit extra sensor 2
VentSettings.S_ExtraSensor3LowLimit R Holding Register (4x) 0805 RW AV, 30805 10 Alarm setting Alarm low limit extra sensor 3
VentSettings.S_ExtraSensor4LowLimit R Holding Register (4x) 0806 RW AV, 30806 10 Alarm setting Alarm low limit extra sensor 4
VentSettings.S_ExtraSensor5LowLimit
R
Holding Register (4x)
0807
RW
AV, 30807
10
Alarm setting
Alarm low limit extra sensor 5
VentSettings.S_SelectedSensor1(0) X Holding Register (4x) 0808 RW AV, 30808 1 Alarm setting Select sensor 1 for high & low limit selected sensor alarm
0 = Not active
1 = A_AI_OutDoorTemp
....
VentSettings.S_SelectedSensor1HighLimit(0)
R
Holding Register (4x)
0809
RW
AV, 30809
10
Alarm setting
Alarm high limit selected sensor 1
VentSettings.S_SelectedSensor1LowLimit(0)
R
Holding Register (4x)
0810
RW
AV, 30810
10
Alarm setting
Alarm low limit selected sensor 1
VentSettings.S_SelectedSensor2 X Holding Register (4x) 0811 RW AV, 30811 1 Alarm setting Select sensor 2 for high & low limit selected sensor alarm
0 = Not active
1 = A_AI_OutDoorTemp
....
VentSettings.S_SelectedSensor2HighLimit
R
Holding Register (4x)
0812
RW
AV, 30812
10
Alarm setting
Alarm high limit selected sensor 2
VentSettings.S_SelectedSensor2LowLimit R Holding Register (4x) 0813 RW AV, 30813 10 Alarm setting Alarm low limit selected sensor 2
VentSettings.S_SupplyPIDFreeze X Holding Register (4x) 0814 RW MSV, 30814 1 Unit setting Freeze supply temperature PID control
VentSettings.S_FanComp1X1(0)
R
Holding Register (4x)
0815
RW
AV, 30815
10
Fan compensation curve
Curve 1 point 1 sensor value
VentSettings.S_FanComp1Y1(0) R Holding Register (4x) 0816 RW AV, 30816 10 Fan compensation curve Curve 1 point 1 setpoint compensation
VentSettings.S_FanComp1X2(0)
R
Holding Register (4x)
0817
RW
AV, 30817
10
Fan compensation curve
Curve 1 point 2 sensor value
VentSettings.S_FanComp1Y2(0)
R
Holding Register (4x)
0818
RW
AV, 30818
10
Fan compensation curve
Curve 1 point 2 setpoint compensation
VentSettings.S_FanComp1X3(0) R Holding Register (4x) 0819 RW AV, 30819 10 Fan compensation curve Curve 1 point 3 sensor value
VentSettings.S_FanComp1Y3(0)
R
Holding Register (4x)
0820
RW
AV, 30820
10
Fan compensation curve
Curve 1 point 3 setpoint compensation
VentSettings.S_FanComp2X1
R
Holding Register (4x)
0821
RW
AV, 30821
10
Fan compensation curve
Curve 2 point 1 sensor value
VentSettings.S_FanComp2Y1 R Holding Register (4x) 0822 RW AV, 30822 10 Fan compensation curve Curve 2 point 1 setpoint compensation
VentSettings.S_FanComp2X2
R
Holding Register (4x)
0823
RW
AV, 30823
10
Fan compensation curve
Curve 2 point 2 sensor value
VentSettings.S_FanComp2Y2 R Holding Register (4x) 0824 RW AV, 30824 10 Fan compensation curve Curve 2 point 2 setpoint compensation