Configuration Manual

Version Document
A
001
A
ccess V4.X Configuration manual
17 (56) 2018-07-11
Block step signal if alam
No
Yes
Operation settings: Data & Settings > Temperature control > Heating (Heating 2)
Sequential control
Each output step has individually settable on and off values in percent of the
control signal. The number of steps is equal to the number of heater/chiller groups.
Minimum on and off times can be set, i.e. the minimum time the step has to be
inactive or active for a change to occur.
Binary control
The heater power outputs should be binary weighted (1:2:4:8 for heating). The
number of loads to be controlled is set. Thereafter the program will automatically
calculate the individual Activate levels. Switching differential and minimum on/off
times can be set. The number of heating steps will be: 2no. of groups-1. In binary
mode, the analogue output signal may be used to fill out between the steps. The
signal will go 0…100 % between the Activate of each step. The load connected to
the analogue signal should have the same size as the smallest of the binary
groups. In the example below there are 4 heater groups (1:1:2:4) and the total
number of heating steps is eight.
As alternative or complement to the above mentioned analogue control, heating
and cooling can be activated in steps. The internal signal is then used to activate
digital outputs for control of the heaters/chillers. Up to four heater outputs and
three cooler outputs can be configured. There are two possible modes:
3.2 Exchangers
Activate: Configuration > Function Configuration > Function Activation> Sequence Configure
type
Example
Order heating sequence:
1. ”Exchanger”
2. ”Exchanger extract”
Y1
=
1
1
2
1
4
1
2
1