AIAS RC Techsheet IMO
24 / 26 | AIAS Room controller - installation and operation instruction
Parameter
number
Description FS
47
Select operating mode for central control:
5
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
5=No central control
48
Min ow at cool output when control mode Heating/Cooling with VAV- control is selected
20%
Min ow at Y3 output when control mode Heating/Cooling/VAV is selected
49 Max ow on Y3 output when control mode Heating/Cooling/VAV is selected and in heating mode 0%
50
Conguration of fan control:
3
0=No control
1=Fan is controlled by heating demand
2=Fan is controlled by cooling demand
3=Fan is controlled by both heating and cooling demand
51 Start signal in % for fan speed 1 on heating or cooling control 5%
52 Start signal in % for fan speed 2 60%
53 Start signal in % for fan spped 3 100%
54 Hysteresis for start/stop of fans 5%
55 State number of speeds for the fan (1, 2 or 3) 3
56 Temperature compensation on AI1 0°C
57 Temperature compensation on UI1 0°C
58 Temperature compensation on internal room sensor 0°C
59 Filter factor for analogue temperature inputs 0,2
60
State NO/NC digital input 1:
00=NO (Normally open)
1=NC (Normally closed)
61
State NO/NC digital input 2:
10=NO (Normally open)
1=NC (Normally closed)
62
State NO/NC universal input 1:
00=NO (Normally open)
1=NC (Normally closed)
63
Manual/Auto Heating
2
output: 0=Off
1=Manual
2=Auto
64
Manual/Auto cooling output:
20=Off
1=Manual
65
Manual/Auto Y3 forced ventilation output:
2
0=Off
1=Manual
2=Auto
Manual mode means that Y3 puts out what is stated in parameter 24
if Y3 is congured as an analogue output.
66
Manual/Auto control of change over mode:
20=Heat control
1=Cool control
67 Heating output in manual mode 0 %
68 Cooling output in manual mode 0 %
69 Controller Modbus address
Factory
set
70
Parity but Modbus communication:
2
0=No parity
1=Odd parity
2=Even parity
71 Modbus time out for character (t1.5), in ms. Should be 1,5 times a character, i.e. at least 2 ms. 3 ms