Installation and operating instructions

10
| Electrical connection
Control output reference (tacho)
Important
The applied voltage and the value of the pull-up
resistor must be selected that the current does
not exceed 20 mA.
Frequency = speed (rpm) * 0,6015
Example:
669 Hz / 0,6015 = 1112,21 rpm
-> 36 impulse / revolution
B = customer side A = fan side
open collector circuit
8.3 Variable-speed fans (Frequency converter / EC motor)
Risk from resonant frequencies.
Only operate the fan outside these speed ranges.
Pass through these speed ranges so quickly that any vibration cannot exceed the admissible resonant frequency
values.
For variable-speed fans, use a permanent vibration monitoring for long-term safe operation.
Operation of the frequency converter
Heating of the motor due to use of a variable
frequency drive must be checked in the application by
the customer.
Avoid running the fan via the frequency converter
below 10 Hz.
Starting time: min. 60 sec.
Commissioning of the frequency converter
Observe the operating instructions of the frequency
converter.
Install the fan and frequency converter as near as
possible to one another.
Use shielded cables.
All components (fan, frequency converter and motor)
must be grounded.
We recommend using all-pole sinus filters.
Never exceed the maximum impeller rotation speed
indicated on the name plate of the fan.
| 003