Manual Axial fan AW C003
Table Of Contents
- 1 General information
- 2 Important safety information
- 3 Warranty
- 4 Delivery, transport, storage
- 5 Description
- 6 Name plate and type key
- 7 Installation
- 8 Electrical connection
- 9 Commissioning
- 10 Operation
- 11 Troubleshooting/maintenance/repair
- 12 Cleaning
- 13 Deinstallation/dismantling
- 14 Disposal
- 15 Commissioning Report
4
| Name plate and type key
6 Name plate and type key
1
Type designation
1
2
3
4
5
2
Voltage/frequency/current/
power
3
fan impeller speed/Capacity/
capacitor voltage/Insulation
class/
4
Article no.
5
Certifications
Table 2 Type key
AW 200 E2
Motor type
E2
2 poled/voltage controllable/1 phased
E4
4 poled/voltage controllable/1 phased
Size
Fan type
AW
Axial fan with a wall plate
7 Installation
Safety information
General safety information
General safety information
♦ Observe 2 Important safety information, page 1
♦ Use installation material with fire resistance classes that meet temperature requirements.
♦ Provide contact and intake protection and ensure safety distances according to DIN EN ISO13857 and DIN 24167-1.
♦ To reduce transmission of vibration to the duct system, we recommend flexible connections from our accessory
range, see chapter Accessories.
Preconditions
♦ Ensure that the fan and all its components are
undamaged.
♦ Fit the fans in such a way that there is sufficient
access for installation, troubleshooting, maintenance
and repair.
♦ Protect against dust and moisture when installing.
♦ Ensure that the information on the name plates (fan
and motor) matches up with the operating conditions.
Important
Damage to the bearings or other parts of the fan can occur.
♦ Do not place a duct bend directly before or after the fan!
♦ Ensure a smooth and constant air flow to the device. Ensure a free exhaust.
7.1 Installation positions
The installation is possible in any mounting position.
AW 200E2–C AW 200E4-C AW 250E2-C AW 250E4-C AW 300E4-C
| 003