Configuration Manual

Version Document
A
001
A
ccess V4.X Configuration manual
26 (56) 2018-07-11
Fan levels
Activate Configuration > function Configuration > Function Activation
Fan levels
Normal
Low-Normal
Normal-High
Low-Normal-High
Select the fan stages to use in operation.
The time settings in the scheduler show only the selected steps.
Setpoints for Fans need to be updated.
Changeover
Configure: Configuration > Function Configure
Changeover 1 sequence for heating Heater
Changeover 1 sequence for cooling Cooler
Changeover 2 sequence for heating disable
Changeover 2 sequence for cooling desible
Operation settings: Data & Settings > In-/output status > Digital input (Analogue output)(digital
output)*
1
Change-over is a function for installations with 2-pipe systems. It makes it possible
to use the same pipe for both heating and cooling, depending on whether heating
or cooling is required.
A special analogue output signal, "Changeover 1 (2)*
2
", is used for Change-over
control. Switching between heating and cooling can be done in two ways. A digital
Change-over input signal “Cooling/(heating) changeover 1(2) is normally used.
Open contact gives heating control and closed contact gives cooling control. If the
input has not been configured, change-over is handled by the internal controller
signal. The output signal (AO “changeover 1(2)” and DO “changeover 1(2)”) will
follow the two regular output signals "Heating" and "Cooling". For heating control,
the digital outputs Heating “Sequence-A start” or “Sequence-A pump” are active.
For cooling control the digital outputs Cooling “Sequence-C start” or “Sequence-C
pump” are activate.
If frost protection sensor has been configured, it will function in the usual way
when heating is active. However, when cooling is active, it will only be used for
indicating temperature.
*
1
Digital input (Analogue output)(digital output) = Digital input, Analogue outputs
and Digital outputs
*
2
Changeover 1(2) = Changeover 1 and Changeover 2