30
| Quick configuration guides
4.14 Support control
4.14.1 Activation
Set Support control to Yes in the from the list of available function in the Configuration > Functions > Func-
tion activation menu.
Overview:
Configuration > Functions > Function activation
04 Apr 13:54
Support control
Yes
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Yes as Support control
4.14.2 Operating settings
Adjust the start/stop limits for support heating/cooling and the min run time for the support control function in the
Data & Settings > Demand control > Support control menu.
Overview:
Data & Settings > Demand control > Support Control
04 Apr 13:54
Min time for support control
20 min
Start heating room temperature
15 °C
Stop heating room temperature
21 °C
Start cooling room temperature
30 °C
Stop cooling room temperature
28 °C
Step by step:
1.
Select Data & Settings from the navigation icons
2. Select Demand control
3. Select Support control
4. Adjust the minimum run time in support control as Min time for support control
5. Adjust the start and stop temperatures for support heating as Start heating room temperature, Stop heating
room temperature
6. Adjust the start and stop temperatures for support cooling as Start cooling room temperature, Stop cooling
room temperature
157618 | A002