Quick configuration guides |
7
4.4 Temperature control type (Room)
4.4.1 Activation
Activate room temperature control.
Select Cascade room temp control as temperature control type in the Configuration > Functions > Func-
tion activation menu.
Overview:
Configuration > Functions > Function activation
04 Apr 13:54
Temperature control type
Room cascade
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Room cascade as Temperature control type.
4.4.2 Configuration
Configure the number of connected room temperature sensors in the Configuration > Functions > Tempera-
ture control menu.
Overview:
Configuration > Functions > Temperature control
04 Apr 13:54
Room temperature sensor
1
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Temperature control
4. Select number of connected Room temperature sensors
157618 | A002