VentSettings.S_FrostProtPGainZone2 R Holding Register (4x) 0869 RW AV, 30869 10 T Unit setting P-band freeze protection zone 2 if running mode
(setpoint=alarm limit+P-band)
4.3-1-00
VentSettings.S_FrostProtSPRunZone3 R Holding Register (4x) 0870 RW AV, 30870 10 T Alarm setting Alarm limit freeze protection alarm zone 3 4.3-1-00
VentSettings.S_FrostProtSPStopZone3
R
Holding Register (4x)
0871
RW
AV, 30871
10
T
Unit setting
Setpoint freeze protection zone 3 if standby mode
4.3-1-00
VentSettings.S_FrostProtPGainZone3 R Holding Register (4x) 0872 RW AV, 30872 10 T Unit setting P-band freeze protection zone 3 if running mode
(setpoint=alarm limit+P-band)
4.3-1-00
VentSettings.S_SAFLowspeedAirFlow(0)
R
Holding Register (4x)
0873
RW
Q
Fan setting
Flow setpoint supply air fan low speed (32-bit float)
4.3-1-00
VentSettings.S_SAFNormalspeedAirFlow R Holding Register (4x) 0875 RW 1 Q Fan setting Flow setpoint supply air fan normal speed (32-bit float) 4.3-1-00
VentSettings.S_SAFHighspeedAirFlow
R
Holding Register (4x)
0877
RW
Q
Fan setting
Flow setpoint supply air fan high speed (32-bit float)
4.3-1-00
VentSettings.S_EAFLowspeedAirFlow(0)
R
Holding Register (4x)
0879
RW
Q
Fan setting
Flow setpoint extract air fan low speed (32-bit float)
4.3-1-00
VentSettings.S_EAFNormalspeedAirFlow R Holding Register (4x) 0881 RW 1 Q Fan setting Flow setpoint extract air fan normal speed (32-bit float) 4.3-1-00
VentSettings.S_EAFHighspeedAirFlow
R
Holding Register (4x)
0883
RW
Q
Fan setting
Flow setpoint extract air fan high speed (32-bit float)
4.3-1-00
VentSettings.S_DelayedStartDXCool
R
Holding Register (4x)
0885
RW
AV, 30885
10
T
Temperature setting
Min setpoint deviation to allow start of DX-cooling
4.3-1-00
VentSettings.S_DelayedStartDXHeat R Holding Register (4x) 0886 RW AV, 30886 10 T Temperature setting Min setpoint deviation to allow start of DX-heating 4.3-1-00
VentSettings.S_HumidityNeutralZone
R
Holding Register (4x)
0887
RW
AV, 30887
10
%RH
Humidity control
Neutral zone humidity room / extract air
4.3-1-00
VentSettings.S_FrostProtFanReduction1(0)
X
Holding Register (4x)
0888
RW
MSV, 30888
Unit setting
Airflow reduction during active freeze protection 1
4.5-1-00
VentSettings.S_FrostProtFanReduction2 X Holding Register (4x) 0889 RW MSV, 30889 1 Unit setting Airflow reduction during active freeze protection 2 4.5-1-00
VentSettings.S_FrostProtFanReduction3
X
Holding Register (4x)
0890
RW
MSV, 30890
Unit setting
Airflow reduction during active freeze protection 3
4.5-1-00
VentSettings.S_FrostProtFanReductionZone1 X Holding Register (4x) 0891 RW MSV, 30891 1 Unit setting Airflow reduction during active freeze protection zone 1 4.5-1-00
VentSettings.S_FrostProtFanReductionZone2 X Holding Register (4x) 0892 RW MSV, 30892 1 Unit setting Airflow reduction during active freeze protection zone 2 4.5-1-00
VentSettings.S_FrostProtFanReductionZone3
X
Holding Register (4x)
0893
RW
MSV, 30893
Unit setting
Airflow reduction during active freeze protection zone 3
4.5-1-00
VentSettings.S_ExtraSensor1HighLimit(0) R Holding Register (4x) 0894 RW 1 Alarm setting Alarm high limit Extra sensor 1 (32-bit float) 4.6-1-00
VentSettings.S_ExtraSensor2HighLimit
R
Holding Register (4x)
0896
RW
Alarm setting
Alarm high limit Extra sensor 2 (32-bit float)
4.6-1-00
VentSettings.S_ExtraSensor3HighLimit
R
Holding Register (4x)
0898
RW
Alarm setting
Alarm high limit Extra sensor 3 (32-bit float)
4.6-1-00
VentSettings.S_ExtraSensor4HighLimit R Holding Register (4x) 0900 RW 1 Alarm setting Alarm high limit Extra sensor 4 (32-bit float) 4.6-1-00
VentSettings.S_ExtraSensor5HighLimit
R
Holding Register (4x)
0902
RW
Alarm setting
Alarm high limit Extra sensor 5 (32-bit float)
4.6-1-00
VentSettings.S_ExtraSensor1LowLimit(0)
R
Holding Register (4x)
0904
RW
Alarm setting
Alarm low limit Extra sensor 1 (32-bit float)
4.6-1-00
VentSettings.S_ExtraSensor2LowLimit R Holding Register (4x) 0906 RW 1 Alarm setting Alarm low limit Extra sensor 2 (32-bit float) 4.6-1-00
VentSettings.S_ExtraSensor3LowLimit
R
Holding Register (4x)
0908
RW
Alarm setting
Alarm low limit Extra sensor 3 (32-bit float)
4.6-1-00
VentSettings.S_ExtraSensor4LowLimit R Holding Register (4x) 0910 RW 1 Alarm setting Alarm low limit Extra sensor 4 (32-bit float) 4.6-1-00
VentSettings.S_ExtraSensor5LowLimit R Holding Register (4x) 0912 RW 1 Alarm setting Alarm low limit Extra sensor 5 (32-bit float) 4.6-1-00
VentSettings.S_FilterGuard3Limit_X2 R Holding Register (4x) 0914 RW AV, 30914 1 Q Alarm setting Supply air pre-filter, filter air flow (reference point for calculation of alarm
limit)
4.6-1-00
VentSettings.S_FilterGuard3Limit_Y2 R Holding Register (4x) 0915 RW AV, 30915 10 P Alarm setting Supply air pre-filter, final pressure drop at filter air flow (reference point
for calculation of alarm limit)
4.6-1-00
VentSettings.S_FilterGuard4Limit_X2 R Holding Register (4x) 0916 RW AV, 30916 1 Q Alarm setting Supply air end-filter, filter air flow (reference point for calculation of alarm
limit)
4.6-1-00
VentSettings.S_FilterGuard4Limit_Y2 R Holding Register (4x) 0917 RW AV, 30917 10 P Alarm setting Supply air end-filter, final pressure drop at filter air flow (reference point
for calculation of alarm limit)
4.6-1-00
VentSettings.S_FilterGuard5Limit_X2 R Holding Register (4x) 0918 RW AV, 30918 1 Q Alarm setting
Extract air end-filter, filter air flow (reference point for calculation of alarm
limit)
4.6-1-00
VentSettings.S_FilterGuard5Limit_Y2 R Holding Register (4x) 0919 RW AV, 30919 10 P Alarm setting Extract air end-filter, final pressure drop at filter air flow (reference point
for calculation of alarm limit)
4.6-1-00
TimePro.TC_FanLowSpeed L Input Status Register (1x) 0000 R BV, 20000 Time channel Low speed active
TimePro.TC_FanNormalSpeed L Input Status Register (1x) 0001 R BV, 20001 Time channel Normal speed active
TimePro.TC_FanHighSpeed
L
Input Status Register (1x)
0002
R
BV, 20002
Time channel
High speed active
TimePro.TC_Extra1 L Input Status Register (1x) 0003 R BV, 20003 Time channel Extra time channel 1 active
TimePro.TC_Extra2
L
Input Status Register (1x)
0004
R
BV, 20004
Time channel
Extra time channel 2 active
TimePro.TC_Extra3
L
Input Status Register (1x)
0005
R
BV, 20005
Time channel
Extra time channel 3 active
Page 38 of 45