| Quick configuration guides
5.14.2 Operating settings
Adjust the start/stop limits for support heating/cooling and the min run time for the support control function in the
Data & Settings > Demand control > Support control menu.
Overview:
Data & Settings > Demand control > Support Control
24 Jun 10:31
Min time for support control 20 min
Start heating room temperature
15 °C
Stop heating room temperature
21 °C
Start cooling room temperature
30 °C
Stop cooling room temperature
28 °C
Step by step:
1.
Select Data & Settings from the navigation icons
2. Select Demand control
3. Select Support control
4. Adjust the minimum run time in support control as Min time for support control
5. Adjust the start and stop temperatures for support heating as Start heating room temperature, Stop heating
room temperature
6. Adjust the start and stop temperatures for support cooling as Start cooling room temperature, Stop cooling
room temperature