Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentActual.A_UnitMode X Input Register (3x) 0396 R MSV, 40396 1 - Unit information Actual unit mode
Modbus
0=Stop
1=Starting up
2=Low speed
3=Normal speed
4=High speed
5=Support heating
6=Support cooling
7=CO₂
8=Free cooling
9=Cool down
10=Fire
11=Smoke
12=Recirculation
13=Defrosting
Bacnet
+1 offset for corresponding Modbus
VentActual.A_UnitModeControl X Input Register (3x) 0397 R MSV, 40397 1 Unit information Indicates what is triggering the current run mode
Modbus
1=Time schedule
2=Manual run
3=Digital Input
4=Alarm
5=External control
6=Service stop
Bacnet
+1 offset for corresponding Modbus
VentActual.A_ActiveSeqType X Input Register (3x) 0398 R MSV, 40398 1 - Unit information Active seq. type
Modbus
0 =Heating
1 =Cooling
Bacnet
+1 offset for corresponding Modbus
VentActual.A_ActiveHeatSeqStep
X
Input Register (3x)
0399
R
AV, 40399
-
Unit information
Active heat sequence
VentActual.A_ActiveCoolSeqStep X Input Register (3x) 0400 R AV, 40400 1 - Unit information Active cool sequence
VentActual.A_ActiveYSeq X Input Register (3x) 0401 R AV, 40401 1 - Unit information Active sequence (SEQ-A to SEQ-J)
1=SEQ-A
10=SEQ-J
VentActual.A_SAFRunTime
R
Input Register (3x)
0402
R
AV, 40402
10
-
Unit information
Total run time supply air fan (hours)
VentActual.A_EAFRunTime R Input Register (3x) 0403 R AV, 40403 10 - Unit information Total run time extract air fan (hours)
VentActual.A_DeIcingTime
X
Input Register (3x)
0404
R
AV, 40404
Unit information
Run time in defrosting mode (minutes)
VentActual.A_NeedRunTime I Input Register (3x) 0405 R AV, 40405 1 Unit information Run time in support control mode (minutes)
VentActual.A_CO2RunTime I Input Register (3x) 0406 R AV, 40406 1 Unit information Run time in CO₂ mode (minutes)
VentActual.A_Y1Sequence
R
Input Register (3x)
0408
R
AV, 40408
10
%
PID output
Control signal sequence-A
VentActual.A_Y2Sequence R Input Register (3x) 0409 R AV, 40409 10 % PID output Control signal sequence-B
VentActual.A_Y3Sequence
R
Input Register (3x)
0410
R
AV, 40410
10
%
PID output
Control signal sequence-C
VentActual.A_Y4Sequence
R
Input Register (3x)
0411
R
AV, 40411
10
%
PID output
Control signal sequence-D
Page 9 of 45