QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008

Table Of Contents
Quick configuration guides |
7
1. Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Pressure as Fan control type.
5.3.2 Allocation
Setup differential pressure sensors.
Select I/O (in-/output) placement for where the differential pressure sensors are connected. Set the sensors’ signal and
corresponding measuring range in the Configuration > I/O allocation settings > Analog inputs menu.
Caution
Do not use the same in- or output for several functions.
Overview:
Configuration > I/O allocation settings > Analog
inputs
24 Jun 10:31
Analog inputs
Device Position
Pressure supply air
Controller
UI2
Pressure extract air Controller
UI1
Configuration > ... > Analog inputs > Pressure supply
air
24 Jun 10:31
Min volt input (Vmin)
0.0 V
Max volt input (Vmax)
10.0 V
Sensor value at Vmin 0.0
Sensor value at Vmax
500.0
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select the input connected to the sensor (e.g. UI2) as position for Pressure supply air
5. Select the input connected to the sensor (e.g UI1) as position for Pressure extract air
6. Select Pressure supply air
7. Set Sensor at Vmin the same as the start point of the sensor’s selected measuring range
8. Set Sensor at Vmax the same as the end point of the sensor’s selected measuring range
9. Set Min volt input (Vmin) and Max volt input (Vmax) to values corresponding to the sensor’s signal type (e.
g. 0…10V, 2…10V etc.)
10.Go back to Analog inputs (use the navigation path Configuration > I/O allocation settings > Analog
inputs)
11.Select Pressure extract air and repeat steps 7 through 9.
157618 | A008